L&T ACB C-POWER OF 800A FAULS TRIPING AT THE TIME OF 110KW
MOTOR STARTS WITH EARTH FAULT RELEASE
Answer Posted / k.prakashchandra
If it is new and under test ,CT might have been provided on
neutral instead of phase.If not , mostly due to pole
discrimination ( all poles not closing simultaneously ).
Disable instant element while closing .
| Is This Answer Correct ? | 0 Yes | 0 No |