Answer Posted / nagarajan
For example 20/25MVA Power Trans -132/6.9kv
1. FLC of Secondary=2092A
2.Phase to Phase Voltage for Secondary=6.9/1.732=3.98Kv
3.NGR =3980/2092=V/I=1.90Ohms for 30sec
It is only for power transformer.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
What is the main purpose of c.f.b.c.boiler
what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?
why dimmerstate always connected in star connection? what will happen if it connected in delta?
We have 250 KW x 2 motors, which are load from 25% to 100% varying load in every minute , so how can we compansate the power factor. pl give your opinions on the above subject.
What is lifting power for 1 wb/m2 and 1 A magnet?
What is the function of NER and NET?
how i calculate the syncrones generator NGR resistance .if we have a 6mw generator line voltage of generator 11kv also line current 393.3 ampere.
Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?
sir, Is their any measuring unit of knoking? please explian?
Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?
WHY IL=IPH IN STAR AND WHY IPH=IL/1.732 IN DELTA? WHAT IS REASON BEHIND IT?
working principle of oil startar
what is 400kv doble circuit quadpole tower?
Is a d.c.compound motor is use as a booster? how?
HOW TO CALLICULATE RESITENCE,REACTANCE AND IMPEDENCE VOLTGE OF TRANSFORMER 13.33 KVA 144/240 VOLTS 93/56 A WITH FORMULA