For testing 33kv cable hipot testing. How much kv we have to
Apply .Give in details.
Answer Posted / michael aliganga
CABLE FACTORY AC TEST VOLTAGE =2E+1kV= 2X35+1= 71kV
DC HIPOT TEST:
CABLE INSTALLATION TEST DURING AND AFTER = ET= EF X 1.8 X 0.8
ET = 71 X 1.8 X 0.8 = 102kV, ICEA DC FIELD TEST VOLTAGE
(ICEA S-97-682) IS 100 kV FOR 35 KV SHIELDED POWER CABLE.
EF=CABLE MANUFACTURERS RECOMMENDED FACTORY AC TEST VOLTAGE
IF NOT AVAIABLE USE 2E+1KV
1.8 AC TO DC CONVERSION FACTOR (QUITE COMMON)
0.8 CONVERSION FACTOR FOR DERATING FROM FACTORY TESTING TO
ACCEPTANCE TESTING.
| Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
What is zero of the system?
what are the specifications we must look at to select a relay for any capacity motor?
If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.
why various test are performed on electrical panels & power cables before commissioning on site & what are these test???
if 6 earth pit value is 1.5 ohm then what should be the number of earth pit to make the value .8 ohm
Where can i get practical knowledge of solar system?
Power Factor Correction Panel (Manual & Automatic)
Why is water motor not taking the pressure? what is the problem?
why current flow to the opposite direction of flow of electrons???????????
I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?
how to carried out tan delta test in 11 KV alternator ?
A jet of fluid strikes a plate What was the force required to counter it?
EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.
Do you know what is dry-out test in x'mer
what is the basic need of domestic loads 1- voltage 2- current