What will the new flow factor if D/P Transmitter is
RE-RANGED from 25" WC to 50" WC
Answer Posted / carl_ellis
Answer:
The flow rate at 50.0"wc will be 141.4% of the flow rate at
25.5"wc.
Reason:
The design maximum flow rate at 25.0" is 100.0% flow rate.
Flow rate is the square root of the percentage of flow at a
given DP.
The flow rate at 25.0"w.c. DP is the square root of 1.00 (or
100%)
If the DP doubles from 25.0 to 50.0, then the DP increases
from 100% at 25.0"wc to 200% at 50.0"wc
The flow rate at 200% DP increases by 141.4% because the
square root of 2.00 (or 200%) is 1.414.
Carl Ellis
Measure First
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
POSSITIVE PULSE IS APPLIED TO AN INVERTER INPUT.THE TIME FROM THE LEADING EDGE OF THE INPUT TO THE LEADING EDGE OF THE OUTPUT IS 10 ns. THE TIME FROM THE TRAILING EDGE OF THE INPUT TO THE TRYLING EDGE OF THE OUTPUT IS 8 ns. WHAT ARE THE VALUES OF tPLH and tPHL?
What is instrumentation measurement?
What is Predictive Maintenance
a flow transmitter [range-0-400mbar] connected in process line. please explain me how to calibrate the flow transmitter , & how to do static error
Difference between ultra sonic flow meter
what is the procedure for auto tune in masoneialn 12300 series displacer type transmitter?
What are the types of control valves available
Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?
Drum level tx with GP4 with zero elevation:7300mmh20 on HP and 8050mmh2o on LP as range but on commissioning the tx readiing is max,Why this reading?
In turbine what does term CDP, NI, NH, HSSOC means.
Identification of ss fittings, pilot valves, relief valve.
How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?
How servomotor controls throttle valve of TURBINE?
flow transmeter accuracy 0.075% of full scale & find ucertainty is 0.025 % so what is maximum limit band of uncertainty
you are on site,the plant trips,you are approached by operations,what do you do?