Dear all... I have 1 0-400 duplex type RTD, I connected the
A side to the temperature indicator and B side to the PLC
panel, but when I have observed then found that The PLC side
temp has the variation. and it was distub to other RTD temp
also. so what can I do.pls help me
Answer Posted / carl_ellis
An offset in readings from separate RTD's can indicate
- a difference in calibration of the analog input devices
- a bad RTD element, one that has drifted out of spec
- a common ground issue with ground loops between the analog
input devices
An RTD is supposed to be ungrounded and the two RTD's in a
duplex element are supposed to be electrically isolated from
one another, so it is unlikely the ground loop is unlikely
unless poor wiring of the extension wire or head wiring has
created a connection to ground.
If you're complaining about a small difference of the
indicated temperatures, then get out your cal gear and cal
the inputs.
To check for a bad RTD, I'd take an ohmmeter and see if any
leg on the A side has any connection to the B side by
disconnecting the wiring from each analog input and check
the resistance. If there's a low resistance, it indicates
some connection from A to B. If the extension wires are
then disconnected and the resistance is checked on the RTD
lead wires and the resistance remains, then it's a bad RTD.
If the resistance goes high (open circuit) then the
extension wire is shorting or making a low resistance
connection somewhere.
Carl Ellis
Measure First
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
hiii.... can any one provide me previous years question paper of hindustan petroleum for instrumentation engineering???
what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .
Draw a group of instruments interlocked to a Pump & Motor?
our kks tagging is crossing more than 12 character please suggest how to take tags in the DCS
What is hp & mp seperator .& what is its working principle ?
my data card only does run in my mobile so how can change it that it run other mobile & computer and i can stor data in my data card
What is the PLC configuration in Cement industry?
How digital input and digital output 's are working in dcs
How r the calculation of process line mpm.
ORP sensor working principle?
What is cut off relay? And why use in PLC and DCS?
Draw a great bridge circuit.
how to calibrate and troubleshooting of leveltroll?
Explain bernoulli’s theorem. State its application.
what is a half wave, full wave, and bridge rectifer.