Dear all... I have 1 0-400 duplex type RTD, I connected the
A side to the temperature indicator and B side to the PLC
panel, but when I have observed then found that The PLC side
temp has the variation. and it was distub to other RTD temp
also. so what can I do.pls help me
Answer Posted / carl_ellis
An offset in readings from separate RTD's can indicate
- a difference in calibration of the analog input devices
- a bad RTD element, one that has drifted out of spec
- a common ground issue with ground loops between the analog
input devices
An RTD is supposed to be ungrounded and the two RTD's in a
duplex element are supposed to be electrically isolated from
one another, so it is unlikely the ground loop is unlikely
unless poor wiring of the extension wire or head wiring has
created a connection to ground.
If you're complaining about a small difference of the
indicated temperatures, then get out your cal gear and cal
the inputs.
To check for a bad RTD, I'd take an ohmmeter and see if any
leg on the A side has any connection to the B side by
disconnecting the wiring from each analog input and check
the resistance. If there's a low resistance, it indicates
some connection from A to B. If the extension wires are
then disconnected and the resistance is checked on the RTD
lead wires and the resistance remains, then it's a bad RTD.
If the resistance goes high (open circuit) then the
extension wire is shorting or making a low resistance
connection somewhere.
Carl Ellis
Measure First
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
Explain the working of rota meter.
which processor is used in dcs.
What types of Instrumentation Related Questions can an Interviewer ask in a Telephonic Interview ?
in which principle pressure tx,level tx ,flow tx,temp tx ,control valve works?
What is the use of GMV in turbine?
What is frequency factor in massflow meter? When using frequency output?
how to calibrate electro pneumatic positioner 8013 mil controls ltd ?gsr
TECHNICAL/ARTITUDE
What is solenoid valve? Where it is used?
what is maxdna ?. explain about the software details.
What are different types of cable?
What are different types of control valves?
what is cems analyzer explain with principle and drawing ?
How to find out the current of two motors having same power consumption but different RPM?
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.