On a 10 KVA UPS we have to provide a DC MCB for Battery bank
of 16 nos (12 V 65 AH).
What Shall be the current rating of DC MCB ?
Answer Posted / naveen kumar.b
Ans:- 60Amps MCB
how:-
for 16 battery net voltage is 192Vdc.
For battery low cut OFF voltage fixed in by all kind of ups is 10.5 each battery . so for 16 battery System battery low cut of votage is 168VDC
( :- at time low battery voltage only Dc current consumption is high, we need to take maximum current consumtion for select MCB)
total load we taken= 1oKVA Full load.
DC voltage at time low battery = 168
current consume (at time of low batter)= 10000KVA /168Vdc
current consumption is 60Amps arround
so 60Amps MCB is required
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
describe the Operation of induction generators from bus bars
Name one of major transformer company in KSA ?
what is mean by D.O. in distribution line poles?
how to erect roof control panel?
how to calculate the fault in substation
what happen if field of dc shunt motor opens? what is function of putting res. in parallel to one phase of 3 phase IM? the power supplied by 5A source in circuit is given by------Watt.
if 12v battery get discharged for 2 months after if we put charge it will charge again?how much time it will take to charge?
why we have to particulary use ACB for below ratings,even available of MCB,MCCB with that range ?
Draw a block diagramof Three UPS systems connected in Parallel mode?
Sir, I have applied for the of Assistant.engineer of NPDCL. please send me all AP TRANSCO AND JENCO solved papers of previous exams . I requested send me the papers to my id as soon as possible (rajanikanth_peddi@yahoo.co.in) (This is very urgent) Thank You,
What is the meaning of dedicated earthing?
if any house we instaled a 1.5 ton ac and its phase cable of wiring is installed but netrual cable of wiring not instaed. my question is that is neutual of house(for other wiring is capable for ac load or a sepeart neutrual wiring required
WHY NUTRAL GROUND SYSTEM USED IN 33KV SYSTEM
Dear sir, iam completed iti ncvt electrician 2000-2002 & diploma electrical eng completed 2008-2010 distance education in rvd university, still i got B licences only but my working company want C licences, how to i get c licencese pls reply me iam in critical situation thank you karthick 9841637803
can we use trip light with bus coupler?