in GEAFOL Cast-Resin trnaformer of 11/.72kv which has
tapping of 11550v,11250,11000,10246v in primary side. To
obtain 700v. which tapping should be used of HV side as we
have 11000v/720v tapping now .
Answer Posted / 7anoter4
If the primary voltage [supplied by Utility] it is NOW 11
kV and your transformer at no-load shows 720 V at its
secondary terminals the ratio primary/secondary voltage is
11/0.72=15.278. If you want to reduce the secondary to 700
V you have to change the ratio to 11/0.7=15.714.
Let's say the rated secondary voltage [at no-load] is 720 V.
That means the ratio 11250/720=15.625 it is the most
suitable and you'll get 11000/15.625=704 V at secondary
terminal [at no-load].
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
How to derive detailed design of Suitable bus Bar for 100A for 6.6KV?
What is stacking factor? What is its approximate value?
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB to another Power DB?
CBCT selection
what are all types of cross section in AC cables?
Give the topology of current amplifier with current shunt feedback?
how to calculate the tarriff for an industry whose kva demand is 10 mva
which mm cable should be used for 1.hp immersible pump motor for the distance of 330 metres?
Is there any reason that we get shock on touching phase wire because the earth is at neutral potential? Is there any reason that the earth is at neutral potential because the neutral is earthed in apower station
The knee point of a current transformer is normally unique and known.So why in the nameplate of a CT they put the minimum value like this Vk> 400v.
what is cause of static electricity? I experience shock when i touch metal equipment in a room ,furher check shows earth leakage showing 80ma at the DB near to the 400 MCCB?
Is any generator is developed which is operated with out diesal or other expensive source?
Hello Friends, How can we recognize the CT Star Point is S1 or S2 in case of Electro Mechanical Relays and what is meant by Restraining coil in relays and what is the purpose of that.. thank you in advance..
How many methods use the load flow solution?
In a tap changing transformer where is the tap connected, is it connected in the primary side or secondary side?