How to calculate rated currennt Of Mcb for 2hp motor...
Answer Posted / shri..
v = 415
hp = 2
PF 0.7
W = 1492
A = (1492)/(415*1.732*0.7)
A = 1044.4 /503.14
A = 2.96 Amps / Phase
Take a MCB c curve type
| Is This Answer Correct ? | 16 Yes | 3 No |
Post New Answer View All Answers
can anyone send me some sample question regarding power grid corp
Two bulbs of 100w and 40w respectively connected in series across a 230v supply which bulb will glow bright and why?
What should be the magnetic balance test values for a 3 phase delta/star connected single primary dual secondary winding transformer (90 MVA / 2 X 45 MVA TRANSFORMER)
i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?
On a 6 KVA UPS we have to provide a DC MCB for Battery bank of 16 nos (12 V 42 AH). What Shall be the current rating of DC MCB ?
sir iam a 3rd yr eee student.no core company comes for recruitment to our college.my aim is to be placed in l and t.tell me the procedures.
Main advantage of auto transformer over two windings transformer is that A it needs no cooling B it uses only one winding C core losses are reduced D it has simple construction
In a flange coupling, the flange bolts are designed for
What safety precaution are to be taken for avoiding electric hazards ?
state the working of discharge lamp?
HOW THE OLTC TRANSFORMER SAVE ENERGY IN COMPARISON TO OFF LINE TRANSFORMER AND IS IT ECONOMICAL TO REPLACE THE OFF LINE TRANSFORMER TO OLTC TRANSFORMER
how can we design robots
Define conversion efficiency of a power amplifier. What is its value for class c power amplifier?
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
what is meant by k-rating in isolation transformer?what is k9, k14 stands for?