We operate a 10 Mw facility and we have been experiencing
several trips due to fluctuations on the MVAR? We have
checked all issues related to the AVR and we have found all
OK? Can anyone help us? The grid voltage, internal voltage,
all regular parameters look ok. MVAR fluctuate and there it
goes the unit? What could be happening? Thanks!
Answer Posted / a.j.pailwan
Please check CT connections, CT Specifications and
saturation of particularly B phase as this CT feed back is
used in AVR during PF control mode while pareller with grid.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Benifits of 3ph 4 wire metering over 3ph 3 wire
How to know about the rating(voltage and other) of induction motor if its name plate is missing at the manufacturing site.
What are the different types of transformers?
salam,hi, i need to know what the spesification of 300amp msb...
What will be advantage if we put some load in neutral of grounded star transformer & loadshortcircuit current,rated current of cable & MCB with example?
What is Electrical Grade Aluminum for Tubular BusBars. i am confused between 6063 and T6 or T5 and what is BS 2898 and BS 159?
WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?
how i calculate the syncrones generator NGR resistance .if we have a 6mw generator line voltage of generator 11kv also line current 393.3 ampere.
Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.
how solar power plant energy meter multiplication factor
How is the connection of the tap changer on the HV side been made?
While testing LA mast,What are the parameter limits ?
What is the difference between the transmission line and distribution line?
I want to calculate how much capacitor we connect to maintain the unity power factor? Is there any formula? Pls give me the answer
what is the efficiency of thyristor