Hello sir
This is prakash from
bangalore i have a doubt why we have to
maintain DG power factor in the range
0.78 to 0.8
Perhaps i f it is increased means what
will happen in DG
Answer Posted / kj
DG's are usually rated at 0.8 PF lagging. There is no
issues with running the DG at another higher or lower
lagging PF. Usually the output kw of the engine is set at
80% of the kva rating. For example a 100 kva DG will have
an engine rated at 80 kw. This will al;low for a full load
current of about 140 amps at 0.8 PF. Increasing the PF
towards unity the maximum load current must be reduced
until it is about 110 amps otherwise the engine will be
overloaded. If the PF is reduced below 0.8 PF the maximum
current must not exceed 140 amps. This means the kw of the
load must be reduced. This is to stop the windings in the
alternator being burnt.
Going to a leading PF will cause voltage instability and
can cause damage to the alternator.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
why there using acb enclosure in big buildings
i want to run 11kv star connected motor in 6.6kv with delta connected throught inverter, is it possible?
why magnetising curve not start with zero voltage?
Can RCD's used to protect the VVVF drive if not why.
Comment on the working principle of operation of a single-phase transformer.
why various test are performed on electrical panels & power cables before commissioning on site & what are these test???
what is the mechanical safety of DG ?
state basic meaning of 'INDUSTIAL AUTOMATION'?
why we take movement of rotor always in counter-clockwise direction in 3-phase induction motors?
What is a slack bus?
WHAT IS THE SIGNIFICANCE OF VECTOR GROUPS IN TRANSFORMER? WHAT WILL BE EFFECT WHEN PHASE DISPLACEMENT CHANGES IN TRANSFORMER?WHAT IS THE NEED TO BE PHASE SHIFT CHANGE BETWEEN THE PRIMARY AND SECONDARY WINDING
How Can I calculate for the photometrics requirements for a street lighting? Data given are: 45 units of 6 meter light pole with 150 watts metal halide lamp, 220 volts and installed in a promenade area.
What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.
What is an 86-P or an 86-A trip
how to determine motor size for a fan application?