Hello sir
This is prakash from
bangalore i have a doubt why we have to
maintain DG power factor in the range
0.78 to 0.8
Perhaps i f it is increased means what
will happen in DG

Answer Posted / kj

DG's are usually rated at 0.8 PF lagging. There is no
issues with running the DG at another higher or lower
lagging PF. Usually the output kw of the engine is set at
80% of the kva rating. For example a 100 kva DG will have
an engine rated at 80 kw. This will al;low for a full load
current of about 140 amps at 0.8 PF. Increasing the PF
towards unity the maximum load current must be reduced
until it is about 110 amps otherwise the engine will be
overloaded. If the PF is reduced below 0.8 PF the maximum
current must not exceed 140 amps. This means the kw of the
load must be reduced. This is to stop the windings in the
alternator being burnt.

Going to a leading PF will cause voltage instability and
can cause damage to the alternator.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

PLS MENTION QUESTIONS ASKED IN IOCL INTERVIEW FOR ELECTRICAL EGG??

1957


What are the site acceptance tests for power cables, DG Sets, LT panels & 30kVA UPS ?

1900


How to select a cable size for particular load?

1333


i have 500 amp inductive load of motors ,,,pleas tell me how can i calculate for capacitor bank for improving my power factor to 99 .....calcullations for capacitor bank,,,,

1155


Why is ignitor used in sodium vapour lamp

2906






What are the material used for resistor?

634


how to calculate differential current when we testing differential relay..suppose we have 1000kw generator,630amp VCB,what value we should put /inject so that relay trip the VCB? PLLZ justify ur comment

1162


why we are not giving the zone 1 trip command to the master trip relay

1082


what is the difference between electrical choke and electronic choke?

2092


Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?

1475


Define peak overshoot.

793


What is the abbreviation of NGT panel

1507


What kind of maintenance is conducted for Transformer

1741


The power supplied to a 50mH inductor from a 120V, 60Hz source will be

4239


substation+ plc system

1626