I work on a electronic positioner transmitter 4211 at the
field.I connect my multimeter in series to get the current
output then I calibrate it to 4ma in 0% of position of the
valve and 20ma in 100% position of the valve.My problem is
in the field I get the correct output current based on my
multimeter but in the dcs they only receive 40% in a output
20ma of this positioner.Then I try to simulate in this
analog card and they receive the equivalent percent on the
value that I simulated.Is ther any possibility to reset the
zero and span of this positioner 4211 fisher.And what other
possibility I can do to fixed this.This is my email add (
landicho_randy@yahoo.com )
Answer Posted / sks
you should check that your AI channel might consist of 3
terminals, 1+,1-, COM. this is the facility provided to
connect both voltage(0-10V) or current(4-20ma) analog signal
introducing to AI module/card.
since you are using current i/p(4-20ma) 1- & COM channels
must be looped with 250ohm resistance first. this might
solve your problem.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how can leve transmetter calibate in feild .and also put cv and flow plz .....
give some question relative instrument fitter?
what is the procedure of O2 sensor(ABB) calibration?
Reason for capillary type dp level transmitter fluctuation
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
what will the sending unit in the fuel gauge utilizes?
How do bending tubing provide better measurement than using tubing fittings such as elbows?
Draw a complete P&ID of a flow suction tank indicating all control & protection equipment. Indicate all its inlets and outlets. Explain the controls for this system
how to calculate range of level transmitter?
anybody having Qatar Petroleum questions for instrument Technician offshore ....please send me
How oil line flow measured?eplain about instruments used and working principle?
Explain the mechanism behind the turbine meter.
why fuse block is not used for AI signal?
describe flow nozzel principle?
How is work 5/2 sov?