T.x range -0.1 to 0.2 milibar,so how much mili ampear at 0.1 milibar?
Answer Posted / karthikeyan kvp
TX range is -0.1mbar to 0.2mbar
span= maximum-minimum
= 0.2-(-0.1)
= 0.3
mA = given value- zero value/ span x 16+4
= 0.1-(-0.1)/0.3 x 16+4
= 0.2/0.3 x 16+4
= 14.66 mA
| Is This Answer Correct ? | 8 Yes | 2 No |