Whether capacitor loads can be connected for testing a
diesel engine at its full load capacity? Is there any
limitation of capacotir load? Which is the best load for
testing DG sets?
Answer Posted / kj
Answer 1 is correct.
Normally a resistive load is used for testing a DG. As most
DG's are rated at 0.8 lagging power factor the resistive
load is calculated at unity power factor load on the DG.
This is usually 80% of the kva rating. This tests the
engine to full load.
Where it is required to test the generator at full load
also an induction load is used together with the resistive
load to give the correct power factor.
Capacitor loads are not normally used as DG's do not
operate safely on leading power factors.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What are the no-load losses for the 11000/415V transformer with the following rated capacity? 1.1500 kVA 2. 2000 kVA 3. 2500 kVA 4. 3000 kVA
why does connected a indutor with mnsformeretering core of current transformer ?
If anyone would like to know or practice for FEWA papers contact me on mohamedrashad2@hotmail.com Just completed the supervisor exam in April 2021
what are the accessories need to be added while doing estimation for the following: 1.MCCB 2.MCB 3.ACB
what are the usual topology of transformers at different substations in the power system and why that particular topology is choosen. what are the limitaions of that topology?
SIR, GIVE ME OPGW SAG CALCULATION FORMULA I AM DAE ELECTRICAL. THANKS
is it possible to turn on the single phase star delta on delay timer using 24 v dc ?
What will happened if the neutral of the (star connected secondry) Xformer disconnected? (if its Above KVA rated one)
I use 20 nos led tube 4feet, in pathway 100mtr approximate, so what size cable i use for lighting
What is bode plot?
What is a slack bus?
How to design the earth grid for lightning protection in an industry
I am applying for NTPC examination.Can we please provide previous paper to my mail prasad.chintala108340@gmail.com
PLS SEND THE RRB CHENNAI MODEL QUESTION PAPER my email id is ganesan98655@rediffmail.com
the site measured knee point voltage of protection class CTs should be greater than rated knee point voltage? what about meetering class CTs. Should it be below the rated knee point voltage?