Whether capacitor loads can be connected for testing a
diesel engine at its full load capacity? Is there any
limitation of capacotir load? Which is the best load for
testing DG sets?
Answer Posted / kj
Answer 1 is correct.
Normally a resistive load is used for testing a DG. As most
DG's are rated at 0.8 lagging power factor the resistive
load is calculated at unity power factor load on the DG.
This is usually 80% of the kva rating. This tests the
engine to full load.
Where it is required to test the generator at full load
also an induction load is used together with the resistive
load to give the correct power factor.
Capacitor loads are not normally used as DG's do not
operate safely on leading power factors.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Is the theorem applicable to ac sources?
Why are lt windings placed near the core?
Dears we deal in Chemical are Plate earthing. Kindly call if any requirement and questions. Tech Earth Solutions Mohit Verma 8791071007
what is the use of commutator in dc motor if we supply ac ? commutator is used to convert ac to dc.and it is used to arrange the flux in unidirectional in case of dc supply. if we give ac as supply to dc motor what is the use of commutator?
Explain how you decide what size of electrical wire do you need?
what is settable hystersis protection? If any body knows plz kindly post the answer..
how many types are their in switchyard or substation(like D,I TYPE), what is differant between them
1.Z transform always lies around ? a) origin b) pole c) zero d) z=1. Multiples Mcqs which is bother me can’t find answers on internet. Some help required with little explanation . Note: this is not homework or related to any test. Thanks
Practical condition in 400KV Sub station:- Breaker(open) , isolator(open), Earthing (close) at both end e.g A & B. Now Open A Stn Earthing than Open B stn Earthing (Which have a 50MVA reactor) , AND suddenly show R,Y,B phase 704KV,573KV,118KV respectively. Que is without closing of breaker how it is possible.???? My Whats app No:07621840498 for Further Discussion. Pls experts suggest.
What is voltage ratio of a transformer?
How to know any size of cable if there are not written on cable? Answer must be theurical not by experience.
What is the tension required for the 25000 CFM AHU belt
what happens to the supply voltage if there is any change in frequency?
wat system call?
how can we select the type of wire.what factors we have to look on it , do we have some formula to calculate it. please guide me on it