Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

One 15kw motor Why we used star delta feeder?why not used DOL
please explain in details

Answer Posted / kj

The star delta starter limits the starting current of the
motor by reducing the voltage across each winding. In star
the voltage is equivalent to the phase to neutral of the
power supply. In delta the phase to phase voltage is
applied across the windings.
With a DOL starter the phase to phase voltage is applied
across the windings. The starting current can be in excess
of 7 times the full load current.
The main reason for using star delta starters is that the
power supply system to the motor does not have to support
the high current needed for DOL starting. If the power
supply is not able to supply the current a voltage dip will
occur affecting all other users on the supply.

Is This Answer Correct ?    11 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I had applied for JE in PSEB, Can you pls send me the Question bank for related to my field

1820


For a stable system, where should the poles of a system be in a root loci plot?

1178


defination of lines

1958


11 kg trivevter meter has rating of -/5amps. And pt ratio11000/110v and is connected with 11kv ct/pt unit of cr ratio 75/5amps. And pt ratio of 11000/110v while checking accuracy of meter with HT Accuchek meter what value of PT ratio and CT ratio to be filled in Accuchek meter

1876


i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value

1875


i want to know how to determine that a surge arrester work properly in 11kv system. and how to test a 12kv surge arrester

2123


What is the function of capacitor in electrical circuits?

987


how to calculate earth fault relay current and CBCT ratio

8277


How do we calculate the Out put voltage of generator, after the excitation is being given?

1884


What happen if 200 KVAR capacitor connected to power continuesly?

2079


i want some interview related questions with their answers which can help for attend the interviews...

1600


what is the difference b/w pvc cu conductor and cu breaded wire..?

3484


what is the function of choke in the flourcent tube lights and why the colour is in white mostly in flourcent tube lights

1895


HOW CAN YOU CALCULATE PRACTICAL EFFICIENCY OF A ASYNCHRONOUS INDUCTIONMOTOR OF 7.5KW,& MOTOR IS RUNNING WITH AVOLTAGE OF 410 VOLTS,& TAKING CURENT OF 13 AMPS

1823


What are the factors influence the choice of an electrc drive?

2024