Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have a question, I visit 01 site and face a problem,
there is 2.5 ton Air Con working, when air con compressor
is running at that time rectifier voltages are increasing
upto 290-295 v and rectifier is giving main high alarm
(rectifier is APC single phase, before starting compressor
rectifier voltages was 230v. when air con is going off
rectifier voltages are decreasing smoothly at its actual
voltages 230v.

Load on Genset phases is this: Red-13.5 amp AC (Air Con
load), Yellow-1.7 amp AC (BTS lights etc.) and Blew-4 amp
AC (telecom system load),
Genset phase to phase and neutral to phase voltages are
also ok.


These are 10 sites having same system and same rectifier
APC brand at every site 02 genset are working but the
problem is same at all these 10 sites.

What will be the reason behind???

Answer Posted / k.prakashchandra

Neutral- shift due to load

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How can a equal potential zone be carried out in conductors?

1332


How to back charge the Gas turbine generator

2148


in the case of 6.6kv motor starter combination contain fuses on it VCB. but in 11KV motor starter combination Fuses are not using in it's VCB why?

2275


Please elaborate th´evenin’s theorem?

1139


Explain what is rated speed?

1131


What is Primary And Secondary Injection Test of Relay and Other Electrical Devices. How IT is carried out.

3491


Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028

1970


What is the BS(British Standard)code for 11kv motor

4976


if flux and load static in dc motor and supply voltage increases 20% then what happened in speed

1900


What is critical disruptive voltage?

1312


If we need 4c× 50mm sq cable but it's not available so we can pull 4c×25mm sq two cables?

1405


what's prime importance of protection in electrical system.if protection system don't work properly what can happen in electrical system?

1910


why the name trunking bus PT

3064


why ss stablity limit is more transient stablity limit?

2184


What are the necessary components of the feedback control system?

1216