after syncnhronistion how generator speed controlled by grid
Answer Posted / kj
The generator is magnetically coupled to the grid
frequency. If the fuel to the generator is increased the
generator will try to increase speed but as it is
magnetically locked to the frequency it will take more load
instead. The reverse will happen if the fuel is decreased.
Under some circumstances the magnetic coupling can be
broken. If this happens the energy from the grid will try
to drive the generator back into synch. This can cause
extensive damage to the generator and/or switchgear.
Therefore protection should be used to stop this from
happening.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is the acceptable value of TAN DELTA and dissipation factor for 11kV, 1.75HP Motor?.
What is non-minimum phase transfer function?
I am EEE student i want to improve my core side skills.how cn i approach it?
how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take
Block diagram of Power line communication?
HI SIR, AM PREPARING FOR RRB FOR SECTION ENGINEER POST. PLZ SEND ME THE PREVIOUS QUESTION PAPERS AND HELP ME. I HAVE NO ENOUGH TIME MY EXAM DATE IS 22ND JUNE.... MY EMAIL ID IS nalla.amarnath@gmail.com
Why DG set is not installed in Terrace ??
If Dg set load increase 25%, How much increase fuel Consumption (15 kva 2 cylinder DG set)
what is the difference between earthing and unearth
my b-tech percentage is 50%. what answer will satisfy the hr ?
WHAT IS FAULT CAPACITY OF HT MOTOR TERMINAL BLOCK? ANY BODY HAVE ANSWER PLZ....POST IT.
how to test reverse power trip?
witch pump used in wtp
If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?
what mean by analog ,digital,numerical meters and relays? say the example?