difference between shunt coil and tripping coil
Answer Posted / andrea vanni
shunt coil is not good for safety purpose use, but only for normal operation (usually to close the brk).
For safety purpose, it is necessary to apply the "fail safe" logic, then an undervoltage release coil shall be used.
usually on MV switchgear we have one closing coil shunt type, and two opening coils undervoltage release operated: one for trip commands, one for normal opening.
| Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
what is formula to cal cute earth pit numbers and size of earth strip used in earthing?
how to apply b license to c license in tneb
we have require a Motor (1500kW, 6.6kV, 50Hz) which shall operate at 1500rpm during 30min and after it shall run on 500rpm during 15min. The same cycle shall be repetitive during the whole working days. Which method is best and economic to achieve such type of task. VFD, VVFD, Pole changing motor etc.
what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?
EXPLAIN THE TRANSFORMER MAINTENANCE?
Define piezo-electric effect?
In MEP Services what are parts of STP and what are there function?
why using transformer and thyristor switch in 3 phase apfc panel
No load tap changing transformer working
how to get electrical supervisour certificate in gujarat
Which thing is maximum in RLC circuit at resonance a)power consumption b)inductive current c)capacitive voltage
Can i use the B-curve MCB instead of C-curve MCB
what is meant by rotating magnetic filed
upto how many load can v connect to stabilizer which is used for tv