A 30KW motor running at 1450 rpm draws 56A, how would you
determine if this is correct or not?

Answer Posted / vipul kumar rai

P=1.732xVoltage x I(current )xPower Factor
30KW=1.732x415xIx0.8
I=30000/(1.732x415x0.8)
I=52.17 AMPS

as per thory 52.17A current draw.
so 56A is approx correct.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how you configure motorvision relay (L&T make)from DCS

4331


how we decide scurt (disc) of insulator with respect to kv rating

2921


is it necessary to earth the rmu before cutting off the transformer winding?if yes why?

1478


what is the chemical name and formula of refrigarent R-134a.

1784


How a capacitor discharge weld power supply works? what is the use of a pulse transformer?

1581






I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1316


what are the industrail measures to over ferranti effect? how would the ferranti effect the power system if those remedial mearsure arent taken? how often does this effect occurs in real power system?

1685


armature is that part in which current is induced since in dc motor we supply current to the conductor so why we call it armature?

1425


How to configure the drives in PLC, through Profibus commnication. And to how to address it?

2365


Do Phase angle measurement have any application in freq/harmonics measurement? If so how?

1466


Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?

1480


how to calculate the power factor when instantaneous voltage and current has harmonics in it ?

1414


what is the principle of the single phase energy meter? and,what is the advantages and disadvantages of single phase energy meter?

3962


what is the k var ratting of 1250kva

1519


what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?

7394