A 30KW motor running at 1450 rpm draws 56A, how would you
determine if this is correct or not?
Answer Posted / vipul kumar rai
P=1.732xVoltage x I(current )xPower Factor
30KW=1.732x415xIx0.8
I=30000/(1.732x415x0.8)
I=52.17 AMPS
as per thory 52.17A current draw.
so 56A is approx correct.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Define de-sensitivity?
what is cathodic protaction?
can i use 2000/5A Clamp meter to measure HT cable
How wire size can define in electrical wiring? What is the ratio?
what is the maintaining Cf in UPS.
what is high - pot test. what's its use?????
why Lightening Arrester Probe sharp at Top of telecom tower.
quantizer means?
how does directional relay work incase of ac ?
The principle of switching circuits for different types of batteries in application of storage systems
What is steady state response?
I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?