A 30KW motor running at 1450 rpm draws 56A, how would you
determine if this is correct or not?
Answer Posted / vipul kumar rai
P=1.732xVoltage x I(current )xPower Factor
30KW=1.732x415xIx0.8
I=30000/(1.732x415x0.8)
I=52.17 AMPS
as per thory 52.17A current draw.
so 56A is approx correct.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
how to differentiate a mpcb,mcb with a contactor? Explain their working operation
How to do stting of vl250 siemens MCCB
hr round
How to calculate multiplication factor in kva example 500kva ans pls ?
Earth has zero potential then what would be the neutral potential ?
what are the 4 rules to start the motor?
(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?
How does the phase sequence controller works, how it identifies the phases? confirm working principle
When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<
State nyquist stability criterion.
where is core-type and shell-type construction suitable for transformers ?
What is a copper loss or i2r loss pc?
Why in power plant projects we see DOL starting method used for motors upto 160 kW instead of star delta method
How to calculate ant test the burden of Current transformer
harmonics filter