A 30KW motor running at 1450 rpm draws 56A, how would you
determine if this is correct or not?
Answer Posted / divakaran a
P=1.732xVxIxP.F
30KW=1.732x415xIx0.8
I=30000/(1.732x415x0.8)
I=52.17 AMPS
sO the current drawing from the motor is 52 amps (Theoriticaly)
in practical the motor may draws more current as based on the load.