In the UVR(Under Voltage Relay) there is a knob for the
hysteresis setting. what is this setting? its threshold is
given from 5% to 50%. please help me....
Answer Posted / kj
The hystersis is the difference between the voltage at
which the relay operates at and resets at.
For example the UVR is set to open the contacts at 200
volts and it can be set to close at 211.5 volts (for 230
volt sensing). This would be 5% hystersis setting.
This is to stop the relay switching on and off continuously
when the voltage is around 200 volts.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
why ahould you show client/engineer activities clearly on the project plan
What is time invariant system?
What is the requirement of grounding the neutral of single phase generators on load? If the neutral is not grounded, what will be the effect?
What is the maximum and minimum rating of UPS?
Do closed loops systems require manual input?
Operation carried out in thermal power stations?
State the methods of improving power factor?
How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?
if an insulated power and control cables of a running gas diesel gensets laid direct in an open trench i.e, trench bed is not rcc of a power house in which rain water, spillage water alwas exists and all power control cables remains submerged even when gas gensets of 480 kw each runningin on load. These power &control cables runs from power house to switchgear room through these trenches in which water remains most of the time. pl explain its merit & de-merit
What is a feedback in control system?
Advantage of LT panel vs HT panel
How does HT work & Voltage required?
how we can set the IDMT relay.
why transformer tank is in rectangular shape what happen when it is in step shape
at which voltage level arcing ground is occurs ??????????