In the UVR(Under Voltage Relay) there is a knob for the
hysteresis setting. what is this setting? its threshold is
given from 5% to 50%. please help me....
Answer Posted / kj
The hystersis is the difference between the voltage at
which the relay operates at and resets at.
For example the UVR is set to open the contacts at 200
volts and it can be set to close at 211.5 volts (for 230
volt sensing). This would be 5% hystersis setting.
This is to stop the relay switching on and off continuously
when the voltage is around 200 volts.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is DC series motor?
What is the rating of circuit breaker needed for 300 KVA load in 33 KV supply line in a transformer of 33 KV / 415 Volt ?
What is minimum phase system?
What is difference between isolator and circuit breaker?
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
What happens if we connect a single phase energy meter in reverse polarity.
What is core CT & it's function?
If two Transformers are connected in parallel having impedance of 50KA in both transformers will the impedance increase or decrease after connecting transformers in parallel?
How we calculate the size of ht cable for any transformer
how to calculate regulation constants for over head lines? and what are the regulation constant for raccoon conductor at different voltage level and different P.F?
Is a 300w induction motor used in a food processor as powerful as a 1000w DC motor.
Actually I have a doubt on neutral and earth.we use Ac power without taking neutral by connecting to earth,but at that time does it affects on efficiency of any electrical components or no? If yes how?
What is the permissible limit of shaft voltage for 6.6 KV motors ? Why? Is there any standard is available?
What is tan delta & PPM in transformer? and whats its IS value?
What is warm / cold start of HT motors. How many warm start & cold start are possible in a day?