why we use 50hz frequency in india why not other frequencies
like 52,59,42 etc
Answer Posted / kj
Other then it being the standard it is because the rpm of
machines is set by the frequency. To generate 50 Hz the
generator must run at 3000, 1500, 1000, rpm depending on
the number of poles (2, 4 and 6). At 52 hz it would be
3120, 1560, 1040 rpm.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
what is mean by transition resistance of transformer?
How does a digital electronic meter work??????
hi,every one, i have to write the search paper on "performance policy optimization" of NGN (next generation networks). i need the material on this topic. can any body help me. please tell me any useful site where the good material is available and name of any reference book. it should be a great help for me.
draw 3 phase rectifier diagram
How to check 11000/1.732 to 110/1.732 Potentila transformer (PT)?
Has someone here done a sizing for a generator (3 phase), its for a pumping station. If you have an example for standby/duty and both running (I) star delta (ii) Soft Starter.
what is buffer resistance starter.?.What is the working principle and where it is used..?
300m long and 30kw inductive loade 3phase supply how many size cable required
What is the Load Capacity of Panther conductor (0.2) and dog conductor (0.2)
why power factor is important?
In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?
Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?
what is the concept of directional power?
What is fault clearing time for Current Limiting Moulded Case Circuit Breaker?.
What is the method for testing the differential protection stabilty in generator? When the time of starting What will happen if differentail protection connection wrong means?