DEAR ALL
I have motors ( 10 units )each one is 90kw 380V 50 HZ 1000rpm
but new local pwer is 220v 60 hz
requierd rpm should be 1000
pleas what the beast solution is used frequncy converter or
rewinding all motos or chang all motors
thanks
Answer Posted / kj
The existing motors cannot be used. Voltage and frequency
is wrong.
The second issue is the speed - 1000 rpm uses a 6 pole
motor at 50Hz. 6 pole at 60Hz is 1200 rpm and 8 pole is 900
rpm.
You will need to change the voltage and frequency.
If the motors are belt drive changing the ratio of the
pulleys will fix the problem of speed.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is the transformer rush current?
we have a lot of model of rectifier but thyristor rectifier is the most rectifier that use in power system. Do you know why this rectifier is used?
Why the output of OP-AMP is always less than Vcc?
How we can calculate the consumption in kwh of motor on basis of kw @100% load, @50% load & @ no load.
Different types of relay fault which phase sequence??
What is the importance of counter based plan & how is it scheduled?
What is the role of feedback in a closed loop control system?
In DC generator, we use commutator, having no. of segments. Then how it is possible to get a half wave of voltage and current for half rotation of armature?
What types of high speed CMOS circuits have you designed?
why we use ac supply as 415 volts instead of 415 v why we cant apply 230 v for dc
how to calculate short circuit current for the busbar
what is the power rating of CPU, CRT type moniter, LCD type moniter,scanner Approx.
What is dc current source? Differentiate between ideal and non ideal current sources?
how to find motors H.P. whout any rating? (only give you a motor and multimeter)
Why wind turbines wheels rotate constantly