DEAR ALL
I have motors ( 10 units )each one is 90kw 380V 50 HZ 1000rpm
but new local pwer is 220v 60 hz
requierd rpm should be 1000
pleas what the beast solution is used frequncy converter or
rewinding all motos or chang all motors
thanks

Answer Posted / kj

The existing motors cannot be used. Voltage and frequency
is wrong.
The second issue is the speed - 1000 rpm uses a 6 pole
motor at 50Hz. 6 pole at 60Hz is 1200 rpm and 8 pole is 900
rpm.
You will need to change the voltage and frequency.
If the motors are belt drive changing the ratio of the
pulleys will fix the problem of speed.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to select correct size of power cable for inverter duty motor

927


what precautions to be taken while desigining a LT,HT panel. Eg-LT panel PCC panel with ACB installed. HT panel VCB panel with VCB installed. & what is main diffrence betwn IP54 & IP55 construction of panel.

2502


in dc series motor if field wdg is shorted then

1445


hwat type of motor is used in thermal gas turbine hydro nuclear power plants and why

1472


how withstand of hi-pot test outputs of transformer wire 2.5mm

1510






Briefing the effects of ASR and ACR of a double closed-loop speed regulating system.

1701


what is alluminium arm in ab conductors

1510


why the neutral line is not giving shock to us if we touch it ?

1348


HOW can i REuse the fused MLL LAMPS & GLS LAMPS at our factory

1430


In the formula : Knee point voltage = Burden X alf / class, Please inform what is alf? regards Shashidhar M.R.

3398


How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540

671


why we get 2 differnet values for power factor in 2 watt meter method in 3 phase

1375


Define sensitivity?

672


write a program that prints prime numbers from 1-20 in digonal form

1528


what is the clear formula to calculate cable size for a load

1484