how much Amp we can put in 1200kva generator?

Answer Posted / vijayakrishnan

KW= KVA X PF
please don't include the P.F
I = KVAX1000/1.732XV
I=1200X1000/1.732X415
I=1669.49
now we will be take only 80%
so we take 1335A only

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Witch do depand of Power factor and theory of power factor?

1655


How to justify this statement ??? "Capacitors in series provide less capacitance but higher voltage breakdown rating for the combination"

1459


The magnitude of sum of two sinusoidal av voltage is equal to 230 volt.the magnitude of each individual voltage is also equal to 230 volt.what must be the phase difference between voltages?

1176


how to caculate cable size for diff types of loads? if anyone know the calculating procedure please tell me

969


If two Transformers are connected in parallel having impedance of 50KA in both transformers will the impedance increase or decrease after connecting transformers in parallel?

1543






If we are given a 10 amp cable type and asked to calculate the number of cores used and the thickness of the cable, how do we do it?? please help...urgent!! i hope the question is clear enough!!

1411


Give me the calculation steps to design an electromagnet to be work in 230V 50 Hz AC Supply. Also give force that is created by that electromagnet when it gets energized.

1818


What is the difference between vector surge relay (78) and Pole slip relay (98G)

646


what is difference between 9kv 5ka surge arrester and 9kv 10ka surge arrester.

1415


placing earthing pit in pathway is correct or wrong??. placing earthing wireGI1/18 inside walls is correct or wrong?. explain!!!

1683


What are m circles?

666


What is a Phase shift meter? Where can I get one?

1662


what is the advantages of having in-built acvvvf (without seperate inverter in the control panel)in the drive system of elevators?

2841


What's mean HVF & HAF in Vacuum Circuit Breaker?

4743


i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value

1421