Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why capacitor bank does not require in DG Set?

Answer Posted / kj

In a single DG the power factor is not a function of the
DG. It is a function of the load. Inductive loads will
produce a lagging power factor and capacitive loads will
produce a leading power factor.
If a capacitor bank is used and the PF on the DG becomes
too far leading the fact that the voltage rise leads the
current rise in the waveform causes induced currents to
flow in the rotor field. This induced current replaces the
current produced by the AVR. As the PF becomes more leading
the AVR does not produce voltage and control of the voltage
is lost. The voltage will rise above the nominal settings
if the PF becomes more leading after the AVR has shut down.

So although it is not normal practice to use capacity banks
with DG's, they can be used as long as the PF remains
lagging.

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In a synchronous motor. if start is running at high speed.  What will be the starting torque : Higher Lower Zero

1670


Why the standard of ambient teperature mentioned as 40 degree celcius in machines.

1910


What is essential to prove safe isolation of electrical circuit?

1048


i need to now what will be the cable size to the following load, transformer to distribution panel distance 110m, load 1000kw, voltage 400v, pf 0.85, permissible voltage drop 2.0%, overhead line, atmospheric temperature 35 degree c.

1587


is it possible to test of bus bar in high rise building without completed full floor ?

1647


RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV is ok ,but haw to calculate the KA rating?

2038


which VFD is better ( LT or HT)

2015


importance of reactive power management

1999


Can a generator runs after getting 1st stator earth fault.

1368


Please brief working principle & construction of permanent magnet AC Servo motor

2186


1. The DC generaror,s induced output emf is connected with a DC motor(as load). when increasing the load of the motor by using brake drum or any way. what are the parameters will changes in both motor and generator(voltage, current, resistance, frequency, speed, torque, power, flux etc...) 2. Similarly for AC generator and AC motor 3. similarly if using DC batteries instead of DC generator, What happens?

2251


What is the formula to calculate the rating of power cable for three phase current.

2083


What is the technical difference between On delay timer and a Star delta timer?

1580


How we can calculate the life of Lead acid battery

1741


What will happened if the neutral of secondary of Xformer ( Star point) Note it's above KVA rated Xformer

1857