Why capacitor bank does not require in DG Set?

Answer Posted / kj

In a single DG the power factor is not a function of the
DG. It is a function of the load. Inductive loads will
produce a lagging power factor and capacitive loads will
produce a leading power factor.
If a capacitor bank is used and the PF on the DG becomes
too far leading the fact that the voltage rise leads the
current rise in the waveform causes induced currents to
flow in the rotor field. This induced current replaces the
current produced by the AVR. As the PF becomes more leading
the AVR does not produce voltage and control of the voltage
is lost. The voltage will rise above the nominal settings
if the PF becomes more leading after the AVR has shut down.

So although it is not normal practice to use capacity banks
with DG's, they can be used as long as the PF remains
lagging.

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is magnetizing current test in power transformer

2186


What is the lower limit of break-down voltage of converter transformer.

1460


what things to be considered when designing UPS

1310


advantage of motor design on higher power factor . normally motors are designed for .8 power factor. what is advantage of designing at .88 power factor

1401


Who many reason of ignition fail ?

1478






What is a fuse? How does it work? What are materials used?

1538


why should the primary of transformer be connected in delta in a heat run test?

1474


How to calculate the electrical load for a standard telecom BTS shelter and choose the DG set capacity for the same load?

2665


How could I get a certificate of competency as Electrical Supervisor? I have completed By BTech in Electrical this year(2012) for VJTI Mumbai Maharashtra. Is it compulsory to be produced while joining?

3014


. What is Electrical Life & Mechanical Life of Circuit Breaker? 2. What is Electrial Life & Mechanical Life of Magnetic Contactor? 3. What is RCD, RCCB & RCBO? 4. What is the Between defferance of RCD, RCCB & RCBO?

2840


WHY DO VOLTAGE TRANSFORMERS FAIL DURING EARTH FAULT IN THE DELTA CONNECTED 6.6KV ELECTRICAL SYSTEM

1554


Please tell me the power flow from pmg to main rotor of an alternator (Including AVR unit)?

1583


What is the drawback of class b amplifier?

658


what are the accessories need to be added while doing estimation for the following: 1.MCCB 2.MCB 3.ACB

1585


How to select the proper VSD to operate high inertial load

1283