Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to can we synchronize different capacity of DG
sets.60kva& 250kva?

Answer Posted / kj

As per the previous answer, synchronising is not a problem.
Using a load sharing module which is set up correctly will
allow the sets to share the load on a percentage basis. In
other words if the load is say 200 kva the load would be
about 65% on each or 38 kva and 161 kva.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I am having dual speed motor of cromton greaves make of 3.7 KW -1400 rpm and 5 KW - 900 rpm. Please let me know groups and winding connction for rewinding purpose.

1993


why the India electrical supply transmission loss is high when compare to us

2034


Briefing the effects of ASR and ACR of a double closed-loop speed regulating system.

2285


how to calculate current carring capacity of cable and cable selection? 1) copper flexible cable 2) copper armoured cable 3) Aluminium cable

1666


For some transformers we are using solid neutral earthing while some others we are using resistance earthing why ?

1955


why ct ,cvt should be stored in a vertical position?

2692


how can i determine the KVA/MVA rating of transformer precisely?? is there any standard test?????

2436


what is the usage of microcontroller in the panel board?

2138


It is desired to flood light the front of a building 42 meters wide and 16 meters hig.Projectors of 30 degree beam spread and 1000 watt lamps giving 20 lumen/watt are availabl.If the desired level of illumination is 75 lumen/m and show a suitable scheme.Assume the cofficient of utilization, deprecitation factor and waste light factor are 0.4, 13 and 1.2 respectively.

3959


new 90kw motor installed so how I purchased cable ,fuse,etc please give me technic for cable selected why always capacitor delta connection

1876


What must be the minimum distance maintained between 2 Generators as per International standards?

2202


r we are using in gas turbine mark (5) frame (6) (made in india Bhel 1997) Ā

1764


The 3 phase Delta connection RB=440V, BY=350V,.......* is Line to Line voltage RY= ? And Formula....?

1761


how is the testing of an REF relay? what are the test REF circuit having?

2043


how to select fuse rating for a 3-phase motor ???

1847