what is fire and gas system?
Answer Posted / ajith294
Fire and gas system usually as part of a saftey system. the
percentage of Lower Explotion limit shall be dectected by
GAS detector and gives the alarm ,normally 20% is High and
40% is High High alarm.
catalytic bead sensor, semiconductor sensor, infrared point
sensor and ultrasonic sensor are using to detect the gases.
there was no establised standared to difine zero air for
calibration. some procedure says pure nitrogen and some
uses sytetic air. But much more realisitc and practical
using ambient air for zero calibration , when area is
considered to be clean.
for span calibration using 2.5 %Methene (CH4) and balance
nitrogen mixer. 2.5 %Methene (CH4)is equal to the 50 % of
LEL.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
How to check vortex flow meter is in good condition while we do not having calibration setup?
principle of automatic votage regulator
i have steam drum height 1000mm. and i want to placed the transmitter below the tap.how i calculate.
Can any one send me IOCL instrumentation question papers.. i dont know the pattern of the questions and what to prepare can any one help me on this .. my email id is anwarnishil@gmail.com
Identification of control valve parts.
Basically iam Instruemntation Engineer, but Iam interested in Instruments design engineering, so plz guide, is there any course, training or Softwres to become Instrument design engineer??.
In turbine what does term CDP, NH, HSSOC means.
How earthing can be checked????
What is the differerence between hysterisis and linearity.
How is automatic reference junction compensation carried out in temperature recorders?
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
please someone tell me what is function of vibration sencer and how many types and how to control viberation.please. my id is jimmykhan077@gmail.com
What is compensation for flow ? Why we use compensation ? What are the factors of different compensation ? We not use then what problems may happen ?
What is cut off relay? And why use in PLC and DCS?
How to calibrate radar type level transmitter for interface level? Total liquid(liq.1 and liq.2), level both the liq individually? For. Both the liquid levels how the signal will go from transmitter to dcs? How to calibrate. Single radar 9:26:55 AM for 2 different liquids in a tank?