In the diesel generator if there is an AVR (auto voltage
regulator) gone faulty, in this condition is there any way
to generate the voltage from the alternator? I need a brief
explanation can you please help somebody

Answer Posted / sheikh

in any type of generators if AVR has become failed
then not possible to generate the voltage, because excitation
is comulsory to megnetized the alternator field winding
in case of AVR faliuer exitation also must be failed becaus
AVR is supplied the exitation volage either no load condition
or on load condition AVR also incrase and decrease the
exitation voltage and current as per demand of load.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to failure indution motor insulation & how to improve heat in motor insulation

1423


1 “earthing” for bonding of equipment and circuits to common plant earth electrode potential, 2 “protective earthing (PE)” when this bonding is required for personal safety provisions 3 “grounding” for interference suppressing bonding of screens, sys-tems with ground level 4. low-impedance earthing ? 5.primary earthing system and secondary earthing system what is that? 6.earthing electrode or mesh net earthing electrode ? very confusing , simple but very informative help required ? i will be very very thankful to you guys.

1612


How to determine alternating current frequency?

695


What is the formula to calculate the rating of power cable for three phase current.

1668


my UPS suddenly goes off and all panel light also blow off.This happens even main electric supply is not interrupted.After some time it automatically starts functioning normally.Batteries are new.

1571






why and how voltage sharing in transformer, during magnetic balance test ?

1809


what is the difference between pvc & fiber glass cables

1050


why are installed water leakage detection system data centers & server rooms

1852


work of choke in florocent tube circuit ?

1658


Hello to all, Please someone can send me HPCL ELECTRICAL Engg. Sample papers to me? Its urjent....my email address is.... raviasiapacific@gmail.com

1649


Is there any guideline say about display of earthing value near to earth pit

710


How to size Air Circuit breaker (ACB)? What is the most important factors?

1797


why did youi choose this career?

1730


i have some screw comprressor with 630kw power,i have established them with simple star to delta circuit,by the way there is so much inertia when the screw comprressors start, can you offer me contactors power with 400vac or any cataluge to choose the contactors

1412


Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.

2295