hw to calculate flc of motor ? data are:3-phase,50Hz,30kw
Answer Posted / pintoo
the data u have given is not sufficient to calculate the
FLC.
the exact formula to calculate FLC is:
P=sqrt(3)*V*I*cos(phi)*efficiency
I=P/[sqrt(3)*V*cos(phi)*eff.]
P=30KW=30000Watt
V=415V
cos(phi)=?
eff.=?
put the value of cos(phi) and efficiency then u will get
accurate FLC.
| Is This Answer Correct ? | 3 Yes | 0 No |