hw to calculate flc of motor ? data are:3-phase,50Hz,30kw
Answer Posted / pintoo
the data u have given is not sufficient to calculate the
FLC.
the exact formula to calculate FLC is:
P=sqrt(3)*V*I*cos(phi)*efficiency
I=P/[sqrt(3)*V*cos(phi)*eff.]
P=30KW=30000Watt
V=415V
cos(phi)=?
eff.=?
put the value of cos(phi) and efficiency then u will get
accurate FLC.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
why occ characteristics of generator is also called as magnatization characteristics ?
if the number of poles generated in stator and rotor side of an induction motor are different then what will happen and why?
stand by earth fault protection (51G) for transformer rating 2000 kVA,Dyn11,33/0.400 V. LV NCT ratio and necessary resistor and metrosil values how to calculate
How to determine stage of Automatic Power factor controlling Relay(Apfcr)?
what is the difference between switchgear and circuit breakers and is there any difference between outdoor and indoor switchgear and circuit breakers , and how would you differentiate between switch yard and substation and grid station . thanks
What is negative sequence over voltage element?
In a voltage-controlled current source A A current booster is never used B The load is always floated C A stiff current source drives the load D The load current equals Isc
Whether 3 phase induction motorwith 100 hp capacity , Amp 160 for which sensitive earth fault relay , type CTUM 15 can be used?
What will be the current drawn by HT motor, if low voltage is applied.. any formula to calculate the LT amps of HT motor.?
What is Traction? 1KVA Alternator, How much urrent taken?
What is the difference between UPS & inverter ? which UPS is better and whos got the edge ? what is the difference between & inverter ? which UPS is better and whos got the edge 12 V , 24 V , 36 V etc what are the advantages of 12 V, 24 V , 36 V etc and what are the disadvantages of 12 V, 24 V, 36 V etc thanks
our factory is going under construction mean time transformer 1000 kva 2 nos &load break swithch 12 kv & 4 nos 750 kva 2 nos & 380 kva 2 nos generator to be errcted.how to arrange earth pits &how to earth connect & neutral pit how to calculate in earth bit size.
what is the difference between megger and earth resister ??
If the rated speed of a d.c. Shunt motor is1440 r.p.m, which method of speed control would you suggested to obtain a speed of 1500 r.p.m?
can anyone please help me to find the rupturing or breaking capacity in KA of circuit breaker (MCCB,VCB,ACB etc) of HT and LT side of a distribution transformer...please help with detailed step by step answer...thank you