Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If the t/f capacity is 500KvA then what is Amps ratting of
the main breaker.

Answer Posted / athar abid

As we Know that

KVA = Sqrt 3 . Voltage(V) . Current(I)

Now for 400V (Phase-Phase) syayem

I = 500KVA/(1.732 * 400)
=500*1000/(1.732*400)
=721.7 Amps

There is no standard breaker available with this rating, so
take one step above rating i.e. 800Amps

Hope its clear.

Regards
Athar Abid

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

For a spring controlled governer the relation F = ar+b (F is the controlling force, r is the radius of rotation a and b are constants), indicates that the governer is

1215


how open delta PT works & what is its construction?

2241


DG cranking voltage?

4751


How to calculate the no of Ceiling fan (1200mm sweep) per unit area?

2067


What should be the magnetic balance test values for a 3 phase delta/star connected single primary dual secondary winding transformer (90 MVA / 2 X 45 MVA TRANSFORMER)

1907


WHAT IS MEANT BY OVER EXCITATION IN GENERATOR TRANSFORMERS? DESCRIBE IT.

2700


what's the difference between 'shaft power demand' and 'BHP' , when we consider electrical load list.

1513


How a capacitor discharge weld power supply works? what is the use of a pulse transformer?

2072


How to select the proper VSD to operate high inertial load

1727


he compression ratio for a petrol engine generally lies between

1279


Is Transol transformer oil comparable to nynas nytro libra?

3102


at what base you will tell the direction of rotation of dc motors and generators?

1134


I Have 3 Phase 10 KW AC Alternator i found one phase weak, so what will be the reason & what action shouls i take to rectify the same.

2064


why lightning arrestor are made in two stack of insulator but why not cvt

2068


WHAT IS VCB SAFETY

1248