If the t/f capacity is 500KvA then what is Amps ratting of
the main breaker.
Answer Posted / athar abid
As we Know that
KVA = Sqrt 3 . Voltage(V) . Current(I)
Now for 400V (Phase-Phase) syayem
I = 500KVA/(1.732 * 400)
=500*1000/(1.732*400)
=721.7 Amps
There is no standard breaker available with this rating, so
take one step above rating i.e. 800Amps
Hope its clear.
Regards
Athar Abid
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
For a spring controlled governer the relation F = ar+b (F is the controlling force, r is the radius of rotation a and b are constants), indicates that the governer is
how open delta PT works & what is its construction?
DG cranking voltage?
How to calculate the no of Ceiling fan (1200mm sweep) per unit area?
What should be the magnetic balance test values for a 3 phase delta/star connected single primary dual secondary winding transformer (90 MVA / 2 X 45 MVA TRANSFORMER)
WHAT IS MEANT BY OVER EXCITATION IN GENERATOR TRANSFORMERS? DESCRIBE IT.
what's the difference between 'shaft power demand' and 'BHP' , when we consider electrical load list.
How a capacitor discharge weld power supply works? what is the use of a pulse transformer?
How to select the proper VSD to operate high inertial load
he compression ratio for a petrol engine generally lies between
Is Transol transformer oil comparable to nynas nytro libra?
at what base you will tell the direction of rotation of dc motors and generators?
I Have 3 Phase 10 KW AC Alternator i found one phase weak, so what will be the reason & what action shouls i take to rectify the same.
why lightning arrestor are made in two stack of insulator but why not cvt
WHAT IS VCB SAFETY