what are the problems are there
if power factor is leading
Answer Posted / sk arman
When the power factor is leading, the capacitive kVAr is
more than the Inductive kVAr and this still has to be
supplied by the source. As kVA is the vector sum of kW and
kVAr, still for the given kW, you have to produce more kVA.
Alternately, for the given kVA, you can only convert
partially into useful work.
Secondary effects are voltage boost in the system,
availability of stored energy to feed the fault in case of a
fault, increase in the asymmetrical component of fault
current, increasing thus the peak value of the fault
current, etc.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what's producer of XLPE cable laying in undergroung
how to select battery for 15 KVA UPS with formula
compare between starting charactristics of synchronous motor with those of 3Q Squirrel cage induction motor
Define filter?
How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?
What is effect of harmonic current (Draw by VFD) on power system/ electrical Equipments ?
what are the available sizes of pin type terminal lugs in the market today?
how to avoid Saturation in C.T?
What is the principal of motor?
Explain the purpose of inductor in an electric circuit?
Cables Construction hi friends, 0.6/1/1.2 kV LV , DC and Control cables are concentric copper conductor what does its means and what is the use of concentric copper conductor,and are this with copper tape shield or copper screening, ? thanks
what is the terminal voltage of dc series generator running at rated speed at no load?
why Y CONNECTION IS BETTER INTERMS OF EFFICIENCY AND P.F FOR A LAOD LESS THAN 40% AND WHY AFTER DELTA IS BETTER FOR > 40%
What products have you designed which have entered high volume production?
how to calculate the mesh earth network resistance in such substation, is there any recommended resistance values with references , thanks!