what are the problems are there
if power factor is leading
Answer Posted / arman
When the power factor is leading, the capacitive kVAr is
more than the Inductive kVAr and this still has to be
supplied by the source. As kVA is the vector sum of kW and
kVAr, still for the given kW, you have to produce more kVA.
Alternately, for the given kVA, you can only convert
partially into useful work.
Secondary effects are voltage boost in the system,
availability of stored energy to feed the fault in case of a
fault, increase in the asymmetrical component of fault
current, increasing thus the peak value of the fault
current, etc.
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
how can i find ct ratio of meter by seeing name plate of meter and how it should be used in MF calculation if it shows only-/1???
What is value of earth resistance required for substation and equipment earthing and what are the reference guidelines
how brushed dc motor operating ?
What is Servo Ventilated Motor?
WHAT IS DIFFERENCE BETWEEN MANUAL CONTROL AND MAGNETIC CONTROL AND STATE ITS ADVANTAGE /DISADVANTAGE
What is dynamo?How it works and what is the function of dynamo in a DG.
How test for Ddo vector group test condition?
The 3 phase 400 hp 440 volt slip ring induction motor do not take one phase amps why ? The motor is running good condition
Define sensitivity?
in my working site. momentary jerck in electrical supply ocurred frequently which cause of multiple losses in our electrical equipements. how can we protect our electrical machines and equipements in this situation.
why wire sizes are 3/29 or 7/29 and why not wire sizes are 2/29 or 6/29?
We need to current density & short circuit calculation at 65kA for aluminium & copper busbar.
what purpose to use excaiter in DG.?
how is capacitor bank look like
what is the operating time for LBB and how does the LBB relay realise whether cb is opened or not?