IN MY INDUSTRIES 125 HP MOTOR USED FOR THAT ONLOAD AMPS UP
TO 280
SO CAN I USE ONE LOWER KVA DG SET WITH STEP UP TRANSFORMERS
THAT MEANS WITH LOW POWER INPUT TO GET CONSTANT HIGH POWER
OUTPUT
EG:125KVA DG SET = 250 KVA STEP UP TRANSFORMERS

Answer Posted / sudhakar g

Generally if u take125HP if we converted in to KW it will come 93.75KW only we can use...

I=(93.75*1000)/(1.732*415v*0.8)

I=163A

this is the maximum current we can use at full Load then how you are using upto 280A....

I think it is not possible...Correct me if i am wrong...

In your second case it is not possible To genrate 125KVA DG set to 250KVA Stepup transformers bcoz if we saw in Generation or transmission of supply the 400KV or 200KV lines there we can use 3 MVA transformers for stepup or Stepdown bcoz the input sully is capable to genrate the supply higher or lower......
According to IS standards the distance between pits must be
2.5mtrs and from the building it should be far from 3000mm

I am taking Electrical desining classes in Bangalore...It
will be usefull for designing as well as site engineers
those who are intrested to go for Electrical
Engineers....we give you indepth knowledge of Load calu,
Cable sizing, Lighting cal, panels, breaker
selection,Autocad drawing....if any body intrested means
pls call to +91-7760362623 or sudhakar28485@gmail.com

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

any one can explain what is the size of pvc,armoured, various sizes of powr cable dia?

1455


what is the safty of poly phase tranformer?

1645


What is the magnetic field (coil DC ) of Turbo Expander?

1592


WITCH CARDS IN USE IN FIRE CONTROL PANEL.

1466


what may the reason for vector shift in a generator?

1407






in 1-phase 230v,how in 3-phase 440v. in each phase in between 230v.

2360


i m in need of current rating chart of heavy duty pvc/xlpe, cu/al cables. can somebody provide me? if yes, plz send me at ashish_patel111@yahoo.com

1532


what is parellel power factor correction?

3437


Which thing is maximum in RLC circuit at resonance a)power consumption b)inductive current c)capacitive voltage

1339


Can any body tell gulf interview question for experienced electrical engineer ?

1630


why should the primary of transformer be connected in delta in a heat run test?

1472


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1409


How to calulate Locked rotor amper(LRA) for compressor type motors?

1298


difference between power surge and switching transient

1536


what are the values of VRY,VYB,VBR,Vry,Vyb,Vbr,Vrn,Vyn,Vbn for Magenetic balance test of 100 KVA and 63 KVA Distribution transformer

2435