Answer Posted / sudhakar g
Hi,
First you want to know how much required for your company or home anything.....suppose we can take 1200w load we required then take 1.5kva inverter
kw=kva x p.f
1200=kva x 0.8
kva=1500
number of SMF batteries=N=6
Voltage of each DC battery = V = 12 V
Ampere-hour of each battery (AH) = X1)
Suppose incase of 2hours usage T=2hours
Volt-Ampere = (N * V * X*EFFicency)/ T
1500 = (6*12*X*0.9)/2
1500 = 33X
X= 43 AH
or else
Time=(number of batteries*voltage of battery*AH)/VA
T=(6*12*43*0.9)/1500
T=1.9hrs
Nearly 100minutes
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS
how u measure/calculate renge of capacitor,capacitor has no any rating tag.what is the theory of measure of capacitons.
What's mean HVF & HAF in Vacuum Circuit Breaker?
How to Calculate KA Rating of Main LT Panel
How to calculate flow of water delivered by pump when pressure & size of pipe line is given
How many capacitors using in LT panel as per Govt rules?
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
What is cut-off rate?
how to changeover ups in this power failur time?
what parameters should we check to reduce the power bill
generally in LT and MV motors we are using 3.5Coresx16,25,35,50 etc cable for supply.although motors is earthed at two point and having all protection.then why we are using that 1/2 core for earthing the motors.while in HT cable we are using only 3core cable for motor supply.generally lt and mv motors are delta connected and ht motors having star connection.whethere it is having any relation with winding connection( star or delta).all motors i am talking about are dol only.can anybody solve my confusion.thanks...
hello! sir i did three year of diploma in electrical (2007- 2010) and now i m a student of electrical engineering. sir can i apply for germany visa for study and part tome work over there?
In the ACB breaker capacity is 2000Amp but this each phase taken 1250 But total beldibg load is 600amp or 700amp watt is the problem
What is the lower limit of break-down voltage of converter transformer.
how many safety really of DG sets.