how we can calculate the transformer size.
Answer Posted / satya mahesh
load factor(LF) and utilization factor(UF) will play a
major role in transformer selection.
Connected load-4810
Maximum demand in a month-1582 Amps
Average load which will be the average of running loads
came in a month-1173 Amps
LF=average load/max demand
=1173/1582
=0.74
UF=No.of hours running Equip/total hours in a month
=(30*20)/(30*24)
=600/720
=0.83
Transformer size= Connected load X LF X UF
=4810 X 0.74 X 0.83
=2954 Amps
for 2954 Amps 2500 KVA(3484 Amps) transformer was suitable
in continution to the future loads also.
Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
how to calculate percentage impedence at 75 deg C at normal tap
What are the types of feedback oscillators?
The screw thread commonly used for transmission of motion is one of the following types of threads
If we have to find the inductance of a dc shunt motor then by giving dc supply or ac supply and what is the reason for it. (this example is from "to determine the transfer function of a dc shunt motor ")
How to dimensioning SDCCH, LAPD and CS7 signaling on GSM?
describe the fully control circuit diagram of ac drives
I have iti elec, 1st aid, and 5 yrs experience in 7.5 mw power plant. Am i eligeble for 11kv license in telangana state..when, how to apply for that.?
in non technical way how can u define POWER FACTOR??
How to test Alternator stability test for REF relay
hi friends how 3 phase converter functioning ?what is working principle of rotory phase converter ?
by using pump duty, how we will can calculate the motor duty(KW)? is there any standard or formula.
What is meant by reverse polarity and how it can be fixed?
technically, what is the reason behind starting the motor star the delta connection .. and what other ways to do this rather than using " star-delta transformer"
Enlist four components of electrive drives.
What is the previous name of Cox's Bazar