how we can calculate the transformer size.
Answer Posted / satya mahesh
load factor(LF) and utilization factor(UF) will play a
major role in transformer selection.
Connected load-4810
Maximum demand in a month-1582 Amps
Average load which will be the average of running loads
came in a month-1173 Amps
LF=average load/max demand
=1173/1582
=0.74
UF=No.of hours running Equip/total hours in a month
=(30*20)/(30*24)
=600/720
=0.83
Transformer size= Connected load X LF X UF
=4810 X 0.74 X 0.83
=2954 Amps
for 2954 Amps 2500 KVA(3484 Amps) transformer was suitable
in continution to the future loads also.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
what is an unbalance in acircuit? in a three phase 3wire circuit how an unbalance will come? in a three phase four wire system how an un balance is coming?
what is conductor copnstant of ab cable
Inverter. converter. Ups.MCB.solar.alternators. motors.
How to know the following data of synchronous generator 1. D-Axis Unsaturated Reactance 2. D-Axis Unsaturated Transient Reactance 3. D-Axis Unsaturated Sub - Transient Reactance
what about the power of wattmeter at starting and loding?
Differenciate between circuit wiring and sub main wiring with illustrations
What is the numerical quantity of sqcm?
what is the operating time for LBB and how does the LBB relay realise whether cb is opened or not?
What is the instrument to check the rotating diode fuse of alternator in running conditions?
how does WTI work ?
why industry prefer ht motor instead of lt motor.
what are the types of electromagnetic forces developed in practical transformer?
oil cooled transformer
My question is whether bellow formula is correct to find bus size for 46kA for 0.5 second & what is RT in bellow formula. formula to calculate the size of busbar to withstand the thermal stresses due to currents with duration of 0.2 sec to 5 sec. Sp = RT( I x I x t) / K Where Sp – is the cross sectional area of bus bar in millimeters. I - is the value of AC fault current. t - is the operating time of disconnecting device in seconds. K – is the factor depending on the material of the conductor, insulation and initial and final temperature. Value of ‘k’ for copper is 143.
describe the fully control circuit diagram of ac drives