how we can calculate the transformer size.
Answer Posted / satya mahesh
load factor(LF) and utilization factor(UF) will play a
major role in transformer selection.
Connected load-4810
Maximum demand in a month-1582 Amps
Average load which will be the average of running loads
came in a month-1173 Amps
LF=average load/max demand
=1173/1582
=0.74
UF=No.of hours running Equip/total hours in a month
=(30*20)/(30*24)
=600/720
=0.83
Transformer size= Connected load X LF X UF
=4810 X 0.74 X 0.83
=2954 Amps
for 2954 Amps 2500 KVA(3484 Amps) transformer was suitable
in continution to the future loads also.
Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
can i use 2000/5A Clamp meter to measure HT cable
Currently what is the highest capacity (MVA) of SPPg generator available in the market?
Why do we perform an open-circuit test and short-circuit test on the transformer?
Why is the frequency not changed during transformation of electrical energy in a transformer?
sir please send me techinical questions for junior engineer posting in bangalore railway i am diploma holder
how hazordious area is classified at an oil & gas plant and categorise suitable class of electric equipment in that area like induction motors, LCS, Lighting Fixtures Fluerescent/Flood lights Mercury& sodium lights, J.Bs, Power Cables etc
Why negative feedback is preferred in the control system?
if two transformers are placed parallel & both have fault impedance of 50KA will it increase or decrease show example?
What is the different between digital phase converter and ordinary phase converter?
What are the roles and responsibilities of electrical engineer in cement plant
is it true there's a big difference in using Cummins or Denyo...especially power output or leakage
Q.1:What protection will be used on HT and LT side of 33/0.4 KV, MVA transformer. Indicate capacities of protective device to be used. Q.2:Which types of back-up protections are used in the power transformers? What do you understand by the term over travel in the relay? Q.3:How star and delta connected winding transformer are provided from earth fault
what are symmetrical and non symmetrical components in electrical installation.
I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?
What is the earth treantment procedure?