Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the disadvantage of leading power factor...why can't
we use it (pf=0) for a long period of time?

Answer Posted / guest

actually We cannot use the pf=0 , at least it should be some value. i mean to say,0.x to 1,
0.1 0.3 0.5 0.7 0.9 1 0.9 0.7 0.5 0.3 0.1
Lagging-> Unity <-Leading

Actually there are three power generated in an electrical system.
1. Active, real or true power which are expressed in kw = sqrt(3)*v*I*cosØ
2. Apparent power expressed in kva = sqrt(3)*v*I
3. Reactive Power expressed in kvar = sqrt(3)*v*I*sinØ
If cosØ(power Factor)=0.99 or -0.99, the sinØ will be same=0.14
If cosØ=-0.8 or 0.8, the sinØ will be same=0.6
If cosØ=-0.5 or 0.5, the sinØ will be same=0.86
According to the above values it is clear that if we go for lagging or leading pf the reactive power generated will be equal.
Kva= kw+kvar,
If use lagging or leading pf the real power (kw)we can use is same. So we must go for nearest value to unity pf to make Kva=kw(this condition satisfies only if Kvar=0 and pf=1) Finally more real power usage.
Then one of my friend told govt is advicing them to use leading power factor , its only because apart from the bulk consumers the domestic users wont use pf correction. In order to compensate we are said to use leading pf.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

wHAT IS CAPACITANCE LATCHING? hOW TO CALCULATE CAPACITANCE LATCHING? hOW TO SOLVE THE PROBLEM IF CAPACITANCE LATCHING APPLIED?

2014


Why earthing is necessary for any equipment?

1728


what will be happen if earth point is being used for as a neutral point for raw power , and same will be used for ups earthing

2081


Define the three phase formula fuse.

1875


How to decide and select the different earthing wire size for the different types of earthing

2279


what are the difference between PLC and embedded

2160


Why electrical power generation and transmission done in 3 phase system not more than 3 phase ?

3079


Draw a 230kv two-bus bar system showing the following. 1.Two generators (150MW) each connected through one 15.75/230KV transformers 2. 1 outgoing lines 3. Two 230/130 KV transformers 4. BUS PT's 5. CT

2591


Make a list observation on Transformer?

2436


how does the thyistor work in dc drive?

1991


For high frequency application we use which transformer?

1940


i am studying in final year can i allowed for 23rd UES of Indian army

2124


Why to keep capacitor bank off while generator running.

1805


WHY RATING OF VCB NOT LESS THAN 630A

2624


What is the power factor of an alternator at no load?

1345