how is a displacer type level transmitter calibrated.explain the method?

Answer Posted / haridass kwt

To calibrate the displacer type LTs by fixed in the w/bench,

First remove the head, clean displacer and chamber and
assemble,

fix the calibration setup (drain isolation, clear tube and
marked scale),

Calculate 100% position of fluid filling, by the Sp.
gravity of the fluid where the LT being used. (Ex: If sp.gr
is 0.8, then the 80% of the displacer height to be marked
in chamber due to the water used for calibration), and mark
every 25% in chamber ouside for reference.

Fill the water and check the transmitter/board/sensor
response approximately.

Fill the water till the displacer touches. and chk 0% and
adjust to 4mA.

Fill the water till 100% to check span and adjust 20mA.

(If the LT s not responding, replace LVDT/board and chk)

Repeat zero and span check 4-5 times and the chk every 25 %
rising and falling.

If ok, the prepare the calibration report and tag it.

Is This Answer Correct ?    11 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the cascade control

1081


1.what is controller proportional gain 2.what is the controller intergral action time. 3.A proportional plus derivative controller that has a proportional band of 20% and a derivative action time of 0.1 minutes. Construct the shape of the output waveform for the triangular input if the input rises and falls at the rate of 4 units per minute.

2322


How d.p. Transmitter can be applied to open tank?

755


How to calibrate RC Feeder system in thermal power station?,If any instrument available to calibrate it,ple inform me. make:stock,

2820


what is actual drum level and compensated drum level?

1849






we have level transmitter for h2s04 storage tank capacity 10k ,always there are failure of transmitter due to failure of magnetic floats ,please come up with solutions at the earliest.

1730


what is diffrance between FF & SMART, explain with difination

2785


how to calculate range of level transmitter?

1876


How to calibrate Field bus transmitter? procedure ?

1917


what are the documents(Construction point of view for a process plant) submitted by contactor initially entering in to new site for client?

1838


when a magnet is heated?

1626


the pump holds on run indication into the dcs and filed local control panel remote push button condition operaton wrong like when the push button pushing conditions the pump is off and the push button release condition the pump is on totally opposite condition . And control room inside give the stop command into dcs just 1secon relay engage and again normal condition. How can I slove

1247


What are advantages and disadvantage of the ac supply load cell?

724


pls give me presant awerness quistion and answer in my emailid.

2439


How to calibration coriolis flow meter?

1388