Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how is a displacer type level transmitter calibrated.explain the method?

Answer Posted / haridass kwt

To calibrate the displacer type LTs by fixed in the w/bench,

First remove the head, clean displacer and chamber and
assemble,

fix the calibration setup (drain isolation, clear tube and
marked scale),

Calculate 100% position of fluid filling, by the Sp.
gravity of the fluid where the LT being used. (Ex: If sp.gr
is 0.8, then the 80% of the displacer height to be marked
in chamber due to the water used for calibration), and mark
every 25% in chamber ouside for reference.

Fill the water and check the transmitter/board/sensor
response approximately.

Fill the water till the displacer touches. and chk 0% and
adjust to 4mA.

Fill the water till 100% to check span and adjust 20mA.

(If the LT s not responding, replace LVDT/board and chk)

Repeat zero and span check 4-5 times and the chk every 25 %
rising and falling.

If ok, the prepare the calibration report and tag it.

Is This Answer Correct ?    11 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the procedure of belt scale calibration?

2442


principle of dead weight tester ?

2074


Why do we have earthing cable in branch cable and shield in the same cable?

2607


please send me some question papers of HPCL aptitude test ?? please send it to bipinb.28@gmail.com ...

1981


I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?

2211


why we use impulse line of flow transmitter at 45 deg. angle both side of orifice plate.

2392


I m appointed as an automation trainee engineer in small firm in that I am only the one , my company give me a project on s7-200 as i m beginner I don't know how to program so please send me the helpful site so that I complete my project before deadline....please help me out in this critical situation.

1796


HOW TO CALCULATE ACCURACY OF AN INSTRUMENT. WHICH IS COMPITABLE FOR USE.

2305


How a conductivity sensor & analyzer work at boiler, whats the principle & science is beyond this,How conductivity sensor sence & convert signal & move toward analyzer & analyzer show reading in percent? also what is temperature compensate option in conductivity analyzer

2786


What is eddy current? Describe the operating principle of proximity probe.

2305


how to work MIL contol valve posistioner ?

2147


What pressure results for a flow transmitter of range 0- 180t/h in the dcs and 0-301mbar in the field using square root extraction. Kindly also suggest formulae for the percentages 0,25,50,75,100?

1927


Hi i am aneesh, done btech in applied electronics & instrumentatiin. And then i took mba in finance & marketing.After that i got placement in finance co and worked there for 3.5 yrs.Now i wanted to come back to engineering job.But without engg experience, i may not able to find an opening.i have done a course related to flow meters and ite calibrations. Kindly suggest where should i try to get a job?

2013


can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.

1919


Please can anybody help for control valve sizing step by step procedure?

2132