Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the differance between normal bybass & maintenance
bybass in UPS?

Answer Posted / ruben

UPS has internal bypass and used if in case there is some
problem within the UPS, ie. overload. the load will be
automatically fed from the bypass circuit. the maintenance
bypass is an external circuit or feeder that is use to feed
the load (bypassing the UPS). this will allow the user to
remove completely remove the UPS from the network/system for
maintenance or replacement.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how is the testing of an REF relay? what are the test REF circuit having?

1939


what is JE exam?

2098


what are the installation procedure of high voltage power transformer,CT,CB&PT?

2008


how can i find cable size from current rating?

1714


What are the advantages of stationary armature and rotating field system?

1159


Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?

1744


what r the checklist while installing 500 kva transformer

2264


How shall i select the value of capacitor or inductor in a system?

1858


does the Trivector Meter of three phase automatically takes care of the low power factor and gives the reading accordigly or it does not take care of the Power factor while giving the readings please explain

1858


WHY TERTIARY OF POWER TRANSFORMERS IS LOADED WITH EQUIPMENTS LIKE CT,PT,ISOLATOR AND CB

1857


In a tap changing transformer where is the tap connected, is it connected in the primary side or secondary side?

1082


What is resistance of 50meters, 16sq.mm, single core copper cable?

1819


I had applied for JE in PSEB, Can you pls send me the Question bank for related to my field

1819


what is PID control in VFD drives?

1933


How to design the NGR Resistance

2019