why we take 4 to 20 mA as out put of every instrument like
pressure transmittre ?why we cant take 0 to 20mA as output?
Answer Posted / vinoth s
If we use 0 to 20ma, then 0 will be the minimum value and 20
will be maximum value.. In case if there is any problem in
the transmitter or in the cables, we get the value 0 but we
think it as a minimum value..we cant able to know that
there is problem in transmitter.. In order to overcome these
constraints, we went for LIVE ZERO concept as 4ma.
0 ma will be consider as DEAD ZERO.
Is This Answer Correct ? | 24 Yes | 0 No |
Post New Answer View All Answers
What is instrumentation instrumentation engineering?
Working principle of magnetic flow meter ......and calibration procedure of e+h magnetic flowmeter...
What is defferent betwen ESP &PCP PUMP .HOW IT IS WORK?
how to calculate range of level transmitter?
What is difference between radial vibration and axial vibration explain in detail .
what is compensation? temprature & pressure
Displace type LT to be calibrated in workshop, wt. 40, dia- 60 mm, density- 0.8kg/cm3.
sir, i preparing hpcl,ongc,barc,hal exams(instrumentation engg)pls send a placement papers
why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V
key phaser where is use and work
what is your eligibility criteria for freashers?
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....
which type of filter gives the constant phase characteristics?
what is the calibration procedure for transweigh make weigh feeder?
when a magnet is heated?