Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why we take 4 to 20 mA as out put of every instrument like
pressure transmittre ?why we cant take 0 to 20mA as output?

Answer Posted / vinoth s

If we use 0 to 20ma, then 0 will be the minimum value and 20
will be maximum value.. In case if there is any problem in
the transmitter or in the cables, we get the value 0 but we
think it as a minimum value..we cant able to know that
there is problem in transmitter.. In order to overcome these
constraints, we went for LIVE ZERO concept as 4ma.
0 ma will be consider as DEAD ZERO.

Is This Answer Correct ?    24 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what are the documents(Construction point of view for a process plant) submitted by contactor initially entering in to new site for client?

2143


Is there any relation between Artificial Intelligence and Instrumentation?

1081


in sulfur process what is material of impulse line we use to connect with transmitter ? and does teflon affected by sulfur?

2221


Define the terms Accuracy, precission, Spam, process tolerance while doing calibration of an instrument? Explaini with an example?

2051


what is The specifications for oriface instalation

2065


How oil line flow measured?eplain about instruments used and working principle?

1990


can any one explain in which term we are flow flow is it volumetric r is it mass? and y

1866


What is the procedure of calibration of Load cell?

1865


sir i m preparing for BARC but i am not getting any papers to prepare for this exam so please send me some sample papers to my i.d for the preparation of barc.

2409


How to do gas analysers calibration in AUTO and Manually by using zero and span gas?

2300


Calibration procedure for water rotameters

2146


What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)

2060


I installed the smartplant instrument v8, but can not be opened, that always said: "INTools 2007 hardlock no found". So Could you help me how to do for that?

2013


How does work A temperature valve or fv control valve in process plz brief me

2378


what is the PC interface and software for connection to ABB logic module “ LM011-CE18RAC “ ( for Programming ) ??

3951