if i conncet ct with ct ratio of 600/5 to an energy meter
having ct ratio of 100/5, the reading show by the meter
will correct, if wrong is there any method to calculate
correct value with shown value, if yes please state
it.....
Answer Posted / wareagle
If the meter is designed to use a 100/5 ct, it will receive
5 amps when the load is 100 amps. If the ct were a 600/5,
the meter would receive only 1/6 x 5 amps or 0.83 amps
which would be a low reading. You would need to multiply
the reading by 6 to get the correct value. You would likely
not get the the exact reading with the 600/5.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What is the significance of integral controller and derivative controller in a pid controller?
Dyn1 transformer vector group testing how to do
what is the function of bearing in dc mchine" and where it is placed
we are having 15kw and 3kw motor both can run in same time , instead of using copper we are using ug aluminium cable , 35 sq.mm is suitable for its current carrying capacity..?
The SFC of an engine is 0.25 kg/kW hr. when the fuel used has a calorific value of 36000 kJ/kg. the thermal efficiency of the engine is
electrical
neutral earth resistance testing is it possible for transformer while in load condition
for a 400kv t/m line with 10 ampere current will corona occur?
What are approaches to tackle sedimentation problem of reservoir?
Thumb rule of cable size(rm>30 rm)X multiplying factor=ampere
sir i applied for hpcl(electrical).i want to know from which subjects most of the technical que will b asked.and pattern of the written test.pls help me
What is the most essential condition for the voltage build up for a d.c. Shunt generator?
what is plunger and what's the use of it in motor alignment?
What are the uses of lead compensator?
Tell me all plants load factors i.e which plant operating on which load?