what is the current rating of 2500 KVA,33KV/433v transformer
on secondary(LT) side
Answer Posted / s bharath
p=1.732*v*i*0.8
2500=1.732*433*i*0.8
i=2500*1000/1.732*433*0.8
i=4.16kA
Is This Answer Correct ? | 6 Yes | 8 No |
Post New Answer View All Answers
how copper and aluminium wires or cables are choose for current rating? please provide copper and aluminium wire selection chart for different current rating ?
Distribution transformer we provided 2 separate earthing pit for Body and 2 separate earthing pit for neutral,we can not connect separate body earthing pit to other earthing pit but we do metal glanding in secondary side cable termination in both side, transformer and PCC panel (LT Panel), is this safe for transformer and other equipment?
How do we calculate the Out put voltage of generator, after the excitation is being given?
what is the maximum permissible limit value of leakage current and leakage counter reading to replace lightining arrester?
what is the formula for computing cable tray size & capacity
why we use condenser in the thermal power plant, althrough the same vapour will be again heated
whatis the commertial spec. of distribution boards ?
full form of flry b
how to extend relay operating timing in 24V dc relay card (without using Timer )
i have applied for the post of RRB section engineering chennai board please send me previou papers and solved answer. my mail id jagarapusrinivas@gmail.com
What is the operating principle of turbo-generator.
Please explain, how to test vector group of tranformer(Delta y1) . Thank
what is difference between earthingpits,earthing grid & earthing mess?
1.what is the difference between transformer differential and busbar differential.2)why we are using 2 slope for trafo diif and 1 slope for busbar diff.3)what is the purpose of metrosil and stabilizing resistor in high impedance relay circuit.4)how metrosil reduce the peak volage.5)what is the funtion of stabilizing resistor
1.dg on load alarm/stop alarm... 2.dg on load. piu alarm alarm kaise chek krte hai