What should be the BDV value of a new transformer oil
Answer Posted / pradyumna chandra panda
For 11kv suppy it is 40kv/2mm at normal temprature is ok. As per my experience it is reach upto 125kv/2mm at 40°c after filtration but we keep it 60kv/2mm NB-Below 24kv/2mm is rejected oil.
| Is This Answer Correct ? | 6 Yes | 1 No |