Answer Posted / prabhu krishna
hipot test is used to test the cable for Its more than
rated voltage level for which it is designed.so, for 11KV
cable 19KV DC is applied for 1 Minute to R&Y,Y&B,B&R lead
of cable one by one & armoring is connected to earth. 11KV
Cable should withstand this voltage.If cable insulation is
weak so it will breakdown at this higher votage
level.Before & After the Hipot test cable meggering should
be done By 5Kv Megger.
| Is This Answer Correct ? | 11 Yes | 1 No |
Post New Answer View All Answers
can i able to get bhel previous exam question paper?
Why in ESP Positive earthed
What is Icu and Ics and what is difference b/w them. please tell me how to calculate a size of a copper bar for a system or a breaker... reply on... king.arish@gmail.com would be waiting for a logical answer.
Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.
Initially, when the input is not equal to the output — what type of response is this?
quantizer means?
what is x'mer ,isolation x'mer & yltra-isolation x'mer?????
From what on-site components does the HT panel monitoring the bus-bars in a 11kV system take inputs?
List the advantages of star-delta starter with induction motor?
what are the problems that generally occur in power flows??
what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?
What are the classifications of heating element?
which of the following elements is not present in stainless steel
if grounding is notdone at regular intervals for long distance transmission, will the load connected at distribution end receive voltage during negativehalf cycle of the sine wave?
sir pls tell me . our ct specifications are 120/5 ,2 core , 0.2 and 5p10 class , 30va and 30va buden. insted of 30 va i want use 15 va. can i use?