Why the voltage n frequency of the incoming generator is kept slightly higher than d grid voltage n frequency while synchronization ?
Answer Posted / raul
Theoritically it is like dat only dat the frequency n voltage of the incoming machine must match the grid frequency n voltage for proper synch, but practically it is kept slightly higher in order to reduce the impact on speed governor n automatic voltage regulator bcoz as the grid pulls d generator into synchronism, there is sudden load applied on d generator due to which there is a dip in both frequency n voltage of d generator which is 2 b corrected by the speed governor by opening d turbine valve more n more steam enters into turbine which corrects d dip in frequency n on d other hand d AVR corrects d dip in voltage by giving d signal 2 d pilot exciter to give more excitation 2 d rotor field winding of d generator.
I hope d concept is now clear 2 u......
| Is This Answer Correct ? | 9 Yes | 3 No |
Post New Answer View All Answers
what is vtg limit of earth and neutral at transformer side?
what is the prinsiple of dc motor and construction and working ,application of dc motor.
How the over load setting for HT Motors calculated-provided in Numerical Relay
How to select a contactor? How many types of contactors are available
Efficient electrical earthing in hard rock area
when will be the iocl interview results ifaced the interview on september 8 th
What are the basic components of the feedback control system?
how to test and calculat the head and discharge in borewell compressor
what r the safety measures in UPS ? explain all?
IF HT CAPACITOR IN ON POSITION IS THERE ANY LOSSES I.S I SQURE OCCURS IN THE SYSTEM
i have applied for junior engineer 2 c&w for Guwahati RRB please send me last five year question paper
Why AC & DC capacitor are use in UPS ??????????????????
In ACS 1000 drive we are using 12 pulse converter,why don't use 3 pulse converter.
what is meant by class 1 E in electrical power supply?
How 3 phase invertor works?