Air pressure in a pressure vessel can rise or fall at up to 2.5kpa/s.The pressure is
sampled every 0.5 seconds.If range of the the pressure indication is 0 to 1500
kPa, what is the max value of the error due to sampling in % of Span
Answer Posted / rizwan afzal
Dear
change in pressure can be +2.5kpa/s or -2.5kpa/s. while
sample rate is 0.5 sample per sec and range is 0 to 1500Kpa
so error is
e=0.5s*2.5kpa/s
e=1.25kpa
now to calculate percentage of error
%e=(100*1.25Kpa)/1500kpa
%e= 0.0833%
keep in mind error can be +0.0833% and -0.0833%
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Hi, Is there any smart plant instrumentation design training institute in Bangalore?
is motorized valve closed when power shutoff?
Can Any body tell me about the Contact or Email id of any good Consultancy which help me to find a job in Instrumentation Field in India .I have Six years of Work Experience in the Same field.Please revert me back on shammi_gwalior@yahoo.com ?
Name different parts of a pressure gauge. Explain the use of hair spring in the pressure gauge.
What is Alpha & Beta fctors related to Orifice Plate & its relation with flow?
Speedtronic system .
Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .
Explain an adaptive / self-tuning controller’s major draw card.
the output of the common trasmitter protocol in qatar gas are the following
What is the minimum rating availalbe for weld neck orifice in market?
How to Calibrate Level Switch in field
Explain plc level and its type?
Reason for capillary type dp level transmitter fluctuation
A PLC is programmed to drive three motors A, B and C as follows : After running motor A for an hour, motor B should get ON and motor A should get OFF. And after running motor B for an hour, motor C should get ON and motor B should get OFF. And after running motor C for an hour, motor A should get ON and motor C should get OFF. (That is, a cyclic repetition with time period one hour) Now, the second condition is: If any motor gone faulty and is tripped, the consecutive motor should get ON and the faulty (tripped) motor should be eliminated from cyclic repetition. The remaining two motors should bear the cyclic repetition of one hour each. (For healthy motor take logic as high and for tripped motor take logic as low) Now, the third condition is: When motor A load(Amps) exceeds 60% of its rated load, motor B should get ON in parallel to motor A. And when both motors A & B are running in parallel, and if their load exceeds 60% of their rated load, motor C should also start in parallel to A & B. [Here the cyclic repetition is eliminated, until their loads become normal(40%)] [Take logic high(1) for load at 60% and logic low(0) for load at 40%] Now draw a flow chart or a ladder diagram to fulfill the above condition.
what is the input to be given in digital flow meter during the the calibration time?