I am having a DG set.The 415 V from Generator is step up to
460 v and then the same is used for Induction furnace.
before Step up, I am connecting LT load to my factory use.
When Induction furnace is in service from DG, when i try to
start a motor, the generator is tripped.Please tell me the
reason.
Answer Posted / r.shanmugasundaram
Induction furnace controller is basically a rectifier cum
Inverter. Generally Rectifiers will generate Harmonics.
Suppose if the DG is not selected to accomodate this non
linear load then the sinusoidal wave form gets distorted
and will trip the DG set or other connected loads which
involves electronic circuitry. May be you can check
with an oscilloscope how the sinusoidal wave pattern
changes when Furnace is switched On. Suppose if the wave
form distortion does not happen then ther could be some
other reason
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
If I want to lift the water at a height 50m from ground level through two inch(diameter) metal pipe then what is the capacity of motor pump is required? is it possible in single phase supply or not?
In an ACB shunt trip coil and undervoltage coil operated normally( breaker open and charged). But closing coil not operating untill manually discharge and recharging. Any help.
What is the voltage gain or transfer function of amplifier?
what is the voltages using in movie theaters??? why ??why not other??
why Induction Generators are not "Black start" ? and apart from WTGs where this types of generator are generally used?
Explain in details how you would react to an unexpected incident when your supervisor or manager is not around to give instructions?
how to meas-our losses for L.T & H.T
Why field rheostat is kept in minimum position while armature rheostat at maximum position?
what is the standard values(Megger test) of resistances between L&N,L&E and N&E for a system on IEE regulations?
How to select the proper VSD to operate high inertial load
What is difference between Sample test and Routine test in safety standard?
How to calculate LT XLPE CABLE for 11 kv / 433 v , 1000 kva oil type transformer system?
Where is the best place to mount distribution panel in a house.
in control scheme dc logic wiring commonly using negative loop,what is the reason?if we use positive looping what will happen?
how to carried out DAR test in 11 KV Alternator ?