Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I am having a DG set.The 415 V from Generator is step up to
460 v and then the same is used for Induction furnace.
before Step up, I am connecting LT load to my factory use.
When Induction furnace is in service from DG, when i try to
start a motor, the generator is tripped.Please tell me the
reason.

Answer Posted / r.shanmugasundaram

Induction furnace controller is basically a rectifier cum
Inverter. Generally Rectifiers will generate Harmonics.
Suppose if the DG is not selected to accomodate this non
linear load then the sinusoidal wave form gets distorted
and will trip the DG set or other connected loads which
involves electronic circuitry. May be you can check
with an oscilloscope how the sinusoidal wave pattern
changes when Furnace is switched On. Suppose if the wave
form distortion does not happen then ther could be some
other reason

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How can we calculate the KVA rating of a Distribution transformer from its core details?

2007


what is earth fault relay 64T, why it is used in main Incomer and neutral CT of Transformer.

3716


What are the operation carried out in thermal power station?

1000


what is the max. acceptable leakage current in 33kv bus bar

2950


What is the type of earth fault protection used in battery? explain.

2235


Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028

1937


Which device is used for the source of emission of electrons in a crt?

1203


why can we use cosine wave instead of sine in ac supply as both have same rms vale and ripple factor

2509


What is Auto Mains Failure Panel & Auto Synchronizing Panel

1881


what is the effect of vector group while phase sequence of a generator changes,whether the vector group changes or not

2058


how to calculate IR value of 33KV cable ??

1822


what is servo motor and how to work it.

1859


If there are two transformer having rating of 2.5mva, 6.6kv/440v(satr-star),and the load is 600kw then what is better to maintain less losses in transformer having both transformer in parellel or only single transformer connected to load? Please give calculated answer

2661


Give details of your interested designation, the post you are interested to serve the company better and explain why you think you can serve the company better in such position if employed?

3289


i have 500 amp inductive load of motors ,,,pleas tell me how can i calculate for capacitor bank for improving my power factor to 99 .....calcullations for capacitor bank,,,,

1557