Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can we do megger test of cable??

Answer Posted / savarkarshriram

If cable is rated for 1.1KV the megger test( Insulation
resistance test) is done with use of 500V or 1000V.
The test probes are connected across each phase , neutral
and ground terminal so that it covers all combinations.

If it is HT cable then 2000V IR tester is used. with the
same method as explained above.
Thumb rule for minimum value is 1M ohm per KV of rated
volatge of equipment

( Mind you megger is name of company and not name of test
so engineers should use term insulation resistance rather
than megger)

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

checking procedure of capacitor based motors.used in fans etc?

2064


PLEASE INFORM ABOUT THE IDEAL TEST RESULTS OF MAGNETIC BALANCE TEST OF TRANSFORMER 33/11 kv DELTA-STAR T/F

2175


diff. between tension mode & speed mode

2265


for what purpose the star point is done in ct

1357


When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<

2094


what is meant by moulded case circuit breaker ?

2130


What is the loss of transformer of 220kv/11kv, 63/80 MVA and 18.05% impedance

1942


What is the need of generator relay panel

2024


What id difference between power and energy?

1257


On 400 amp factory load how kvarh capacitors provide

1655


Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir

1851


why we use copper earthing for neutral while for body GI.

6051


how to make an earthing certificate

2182


what is the AC Plant and how can do the work with parts and picture tell us 150 Tr

1972


PLEASE SEND ME NTPC RELATED INFORMATION LIKE WHICH TOPICS HAV MORE SCOPE,BOOKS TO READ,CUT OFF...PLEASE.mail at thiru.1203@gmail.com

2047