IF THE OUTPUT OF A 100KVA, 415V GENERATOR IS STEPPED UP TO
11KV WITH A 500KVA TRANSFORMER,CAN THE TRANSFORMER BE
LOADED ABOVE THE SOURCE GENERATOR RATING?
Answer Posted / ben
firstly a 100kVA 3-phase WYE generator will only produce 100kVA of power, this will also more than likely be rated at 0.8 power factor meaning the true power you will receive will only be 80kW.
if you are using a 500kVA, 415V/11000V step-up transformer you will probably find that the 100kVA generator is not large enough to saturate the transformers magnetisation current. i would have to say you need either a larger generator or a smaller transformer to suit your site needs.
In answer to your questions: No it can not.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is transmittance?
What do you mean by cogeneration? What its working principle?
What are the advantages and disadvantages of the ac motors?
What are the specifications for conducting earth leakage test as per IEC standard?
What is the relation between frequency and motor rpm?
Enlists the applications of sampled data systems?
Explain the operation principle, advantages and disadvantages of the following converters: a) A 12 pulse converter b) A Switch-mode inverter c) A thyristor inverter
what is meant by class 1 E in electrical power supply?
How to design the NGR Resistance
How to calculate energy stored in an inductance?
what is the IS foe lightning arrester?
Explain with example of functional requirements of protection relay in terms reliability, selectivity, sensitivity
when will be the iocl interview results ifaced the interview on september 8 th
I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?
in science exhibition how lamp can blink when you clap near the lamp ? thank you