How to calibrate a temperature transmitter & how a Cold junction Compensation will be carried out?
Answer Posted / noori
Hi
there are two methodes of temp.tx calibration:
1 - if u have MV sourse u have to get ambiante temp.MV & the
temp. you select and using themocouple vr. MV chart to get
the corresponding MV for these two temps.and for the same
thermocouple type
you have to subtracte the MV for ambiant from the MV for
your temp.
then yiu can inject this new MV to the input of the Tx
you have to get two tempretures for the calibration one for
ZERO &the second for span
you have to do the above prcedure for both points
2 - if you have temperature calibrator the you have to use
the same type of thermocouple immering it directly in the
calibrator and set the first point for Zero & set the second
point for span adjustment
Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
how can leve transmetter calibate in feild .and also put cv and flow plz .....
Why grounding is necessary? Give example with diagram.
Make Heater Process Logic.
Operational amplifiers
where uses EXe /EXd/Exo/Exn/Exp/Exq/EXia
why would you like to join our company
why any measurement made interms of pressure is more accurate ? to be more precise most of the flow velocity is made interms of pressure and it is accurate. what is the reason behind pressure measurement being accurate ?
1)How many tpes of vibration probe and how many tpyes of vibration. 2)how we can calibrate a vibration probe with tk3 3)what is RMS value in vibration measuring application and how we calculate it.
Gas equation
Which Signal hart communicator work? If there any signal change when hart connect while transmitter in line ?
who's take first position in process in the timing of new installation flow transmitter and control vavle. give the answer with logical trick.
There are two chlorination tonners both are connected to two pressure swithes and the pressure switch is connected to SOV which operates the valve to changeover the tonner selection i.e if pressure one tonner goes low the other tonner should come in line if it is inautomatic selection design a circuit using relays ?
while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
What materials are used in thermo wells?