there is a # KVA Transformer of 11 KV/440V, in simple(not use formuia) how can you calculate it's HT & LT side current.

Answer Posted / guest

Dear P.Kalivada 100KVA transformers total power (3 phase) is 100KUA one phase give 33KVA, Phase voltag is 11/1.732 = 6351 volt therefore current is 33000/6351=5.1 amp (at unit pf). You can see a name plate of 100KUA 11KV/433v tranrsformer it is written 5 amp as HT Current and 133 amp as LT side current you can verify any tranformer whose primary voltage is 11KV it's current is approximately to #/20 and secondary side of 433V it's current is approxhmately to # +#/3 ( # is how much KVA)

Is This Answer Correct ?    17 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What type of a DC motor would you use for a lift?

669


What is Delta Connection? What is meant by Forward Delta & Reverse Delta & How Will be the Connection in Power Transformers?

1813


What is the formula to calculate distribution transformer De-rating on iron losses basis

1357


What is the HVDC Transmission System? What are the conditions applicable to lay an HVDC Line?

1865


How to calculate flow of water delivered by pump when pressure & size of pipe line is given

1784






why the colour of insultor stack , petticoat is brown. Is it has some technical reason.

1575


I have a relay contact rated at 220v dc which is supplied with a 24vdc from the panel,for it to trip the dampers(24vdc).What if the application of the relay changes so that it should work at its rated 220vdc then will it work at 24vdc supply given or any other consideration needs to be taken .....

1652


Hello to all, Please someone can send me HPCL ELECTRICAL Engg. Sample papers to me? Its urjent....my email address is.... raviasiapacific@gmail.com

1645


What are the different types of LT Cables?

628


what is a power factor?

1320


What range of speed can you get with the field control method of speed control of d.c. Shunt motor?

666


The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.

1577


A 10 MVA, 66KV, 50Hz, Y-connected 3-phase alternator has synchronous reactance of 0.635 Ù. It is working at full load at 0.8 lagging p.f. condition. Find torque angle, neglect armature resistance.

2081


which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured

1061


what is consequences of neutral and earth connect?

1661