What will be the full load current of 60KVA UPS. Suggest
for this formula.
Answer Posted / murugesh.k
60kva x 0.8=48kw or 48000watt
we know p=1.732xVIcos@
I=p/1.732xVcos@
I=48000/1.732 X 415v X 0.8(Where V=415v)
I=48000/575
I=83Amps
So Full load current is 83 Amps.
| Is This Answer Correct ? | 4 Yes | 2 No |
Post New Answer View All Answers
in science exhibition how lamp can blink when you clap near the lamp ? thank you
what is the purpose of high speed earth switch in gas insulated substat
what is the meaning of 0.5ohm Resistance
what is difference between bus coupler and auto transfer switch
why we need to us lenz's law for synchornous motor
WHY THE COLOR OF OUTDOOR TRANSFORMER IS BLUE ONLY???
WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.
what is the isolation transformer. what is the isolator?
how we find transformer capacity by ohm
A jet of fluid strikes a plate What was the force required to counter it?
how to decide choke rating for drive?
Whether should be the oil level in OCTC transfomer? It should be upto winding immersed completely or should be upto tap changer s/w? How it will affect the performance of the transformer. Rating may be 33KVA
what is the formula for calculating the phase clerance between two phases and phase to earth how to calculate the cable for a motor
what is photo voltic cell,& what are the materials associated with that?and any spcifications like volts/cm etc?
how i can calculate the size for fire cable